Publication 1766-RM001A-EN-P - October 2008
ASCII Instructions
391
7
0x07
The instruction cannot be executed because the
communications channel has been shut down via the
channel configuration menu.
Reconfigure the channel and retry operation.
8
0x08
The instruction cannot be executed because another
ASCII transmission is already in progress.
Resend the transmission.
9
0x09
Type of ASCII communications operation requested
is not supported by the current channel
configuration.
Reconfigure the channel and retry operation.
10
0x0A
The unload bit (UL) is set, stopping instruction
execution.
None required.
11
0x0B
The requested number of characters for the ASCII
read was too large or negative.
Enter a valid string length and retry operation.
12
0x0C
The length of the Source string is invalid (either a
negative number or a number greater than 82).
Enter a valid string length and retry operation.
13
0x0D
The requested length in the Control field is invalid
(either a negative number or a number greater than
82).
Enter a valid length and retry operation.
14
0x0E
Execution of an ACL instruction caused this
instruction to abort.
None required.
15
0x0F
Communications channel configuration was changed
while instruction was in progress.
None required.
Table 21.4
Error Code
Description
Recommended Action
decimal
hexadecimal