Publication 1766-RM001A-EN-P - October 2008
Fault Messages and Error Codes
579
0005
Reserved
N/A
N/A
0006
MEMORY MODULE
HARDWARE FAULT
The memory module hardware
faulted or the memory module is
incompatible with OS.
Non-User
•
Upgrade the OS to be compatible with
memory module.
•
Obtain a new memory module.
0007
MEMORY MODULE
TRANSFER ERROR
Failure during memory module
transfer.
Non-User
Re-attempt the transfer. If the error persists,
replace the memory module.
0008
FATAL INTERNAL
SOFTWARE ERROR
An unexpected software error
occurred.
Non-User
•
Cycle power on your unit. Then,
re-download your program and re-initialize
any necessary data.
•
Start up your system.
•
Refer to proper grounding guidelines and
using surge suppressors in your controller’s
User Manual.
•
Contact your local Rockwell Automation
representative if the error persists.
0009
FATAL INTERNAL
HARDWARE ERROR
An unexpected hardware error
occurred.
Non-User
•
Cycle power on your unit. Then,
re-download your program and re-initialize
any necessary data.
•
Start up your system.
•
Refer to proper grounding guidelines and
using surge suppressors in your controller’s
User Manual.
•
Contact your local Rockwell Automation
representative if the error persists.
000A
OS MISSING OR
CORRUPT
The operating system required for
the user program is corrupt or
missing.
Non-User
•
Download a new OS using ControlFlash.
•
Contact your local Rockwell Automation
representative for more information about
available operating systems your controller.
000B
BASE HARDWARE
FAULT
The base hardware faulted or is
incompatible with the OS.
Non-User
•
Upgrade the OS using ControlFlash.
•
Replace the Controller
(MicroLogix 1100,
MicroLogix 1200, MicroLogix 1400)
.
•
Replace the Base Unit
(MicroLogix 1500
only)
.
•
Contact your local Rockwell Automation
representative for more information about
available operating systems your controller.
0011
EXECUTABLE FILE 2 IS
MISSING
Ladder File 2 is missing from the
program.
Non-User
•
Re-compile and reload the program.
0012
LADDER PROGRAM
ERROR
The ladder program has a memory
integrity problem.
Non-User
•
Reload the program or re-compile and
reload the program. If the error persists, be
sure to use RSI programming software to
develop and load the program.
•
Refer to proper grounding guidelines and
using surge suppressors in your controller’s
User Manual.
Error Codes
Error
Code
(Hex)
Advisory Message
Description
Fault
Classification
Recommended Action