Publication 1766-RM001A-EN-P - October 2008
452
Communications Instructions
Network Message Example 2:
MicroLogix 1400 Ethernet to SLC 5/03 DH485 via ENET, DHRIO and
1785-KA5 bridge device
The following illustrates the MicroLogix 1400 (CH1 Ethernet) sending a
remote message to a SLC5/03 processor (DH+ Node 51). The remote
message will passthru an ENET module, a ControlLogix chassis
(Gateway), a DHRIO module and a 1785-KA5 bridge device. In order for
the message to pass through the network, a multiHop MSG must be set up
and a DHRIO Routing table must exist. It must route to a DHRIO module
onto DH+ thru a 1785-KA5 bridge to DH485. Follow the example below
for the configuration steps.
Adding 1785-KA5 bridge module
Routing to a DHRIO module onto DH+ thru a 1785KA5 bridge to DH485.
In order for the RSLinx, RSWho window to browse the DH485 network
you must configure the 1785KA5 bridge in the ControlLogix Gateway
Configuration software (1756gtwy). Follow the example below for the
configuration steps.
To go from a DHRIO module through a 1785-KA5 bridge device to a
DH485 network, the DHRIO module must be configured using the
ControlLogix Gateway Configuration tool. For example, if a 1785-KA5
bridge is on a DH+ network at node 37 and the DH485 LinkID is 13,
complete the following:
Ethernet Hub
100.100.115.1
100.100.115.7
Backplane
Link ID 20
Link ID 27
DHRIO Link ID 24
ML 1400
SLC5/03 & KFC
DF1
1785-KA5
Control Logix Gateway
51
7
A
B