Publication 1763-RM001B-EN-P - April 2007
Communications Instructions
401
and a DHRIO Routing table must exist. It must route to a DHRIO module
onto DH+ thru a 1785-KA5 bridge to DH485. Follow the example below
for the configuration steps.
Adding 1785-KA5 bridge module
Routing to a DHRIO module onto DH+ thru a 1785KA5 bridge to DH485.
In order for the RSLinx, RSWho window to browse the DH485 network
you must configure the 1785KA5 bridge in the ControlLogix Gateway
Configuration software (1756gtwy). Follow the example below for the
configuration steps.
To go from a DHRIO module through a 1785-KA5 bridge device to a
DH485 network, the DHRIO module must be configured using the
ControlLogix Gateway Configuration tool. For example, if a 1785-KA5
bridge is on a DH+ network at node 37 and the DH485 LinkID is 13,
complete the following:
DHRIO Routing table creation