Publication 1763-RM001C-EN-P - October 2009
Sequencer Instructions
243
Addressing Modes and File Types can be used as shown in the following
table:
SQO- Sequencer Output
Instruction Type: output
On a false-to-true rung transition, the SQO instruction transfers masked
source reference words or long words to the destination for the control of
sequential machine operations. When the rung goes from false-to-true, the
instruction increments to the next step (word) in the sequencer file. Data
stored there is transferred through a mask to the destination address
specified in the instruction. Data is written to the destination word every
time the instruction is executed.
The done bit is set when the last word of the sequencer file is transferred.
On the next false-to-true rung transition, the instruction resets the position
to step one.
SQC Instruction Valid Addressing Modes and File Types
For definitions of the terms used in this table see Using the Instruction Descriptions on page 82.
Parameter
Data Files
Function Files
CS - Comms
IO
S -
I/O
DL
S
-
Dat
a
L
o
g
Address
Mode
(1)
Address Level
O
I
S
B
T,
C
, R
N
F
ST
L
MG,
PD
RI/R
IX
PL
S
RTC
HS
C
PTO, PWM
STI
EII
BH
I
MMI
LC
D
Imme
diate
Di
re
c
t
Indir
e
c
t
Bi
t
Wo
rd
Long
W
o
rd
Eleme
n
t
File
•
•
•
•
•
•
•
•
•
•
Mask
•
•
•
•
•
•
•
•
•
•
•
•
Source
•
•
•
•
•
•
•
•
•
•
•
Control
(2)
•
•
Length
•
•
Position
•
•
(1) See Important note about indirect addressing.
(2) Control file only.
IMPORTANT
You cannot use indirect addressing with: S, ST, MG, PD,
RTC, HSC, PTO, PWM, STI, EII, BHI, MMI, CS, IOS, LCD,
and DLS files.
EN
DN
SQO
Sequencer Output
File
#B3:0
Mask
N7:0
Dest
N7:1
Control
R6:0
Length
1<
Position
0<
SQO
Execution Time for the SQO Instruction
Controller
Data Size
When Rung Is:
True
False
MicroLogix 1100
word
23.78
μ
s
6.21
μ
s
long word
24.4
μ
s
6.21
μ
s