Timer and Counter Instructions
How Counters Work
The figure below demonstrates how a counter works. The count value
must remain in the range of -32,768 to +32,767. If the count value goes
above +32,767, the counter status overflow bit (OV) is set (1). If the count
goes below -32,768, the counter status underflow bit (UN) is set (1). A
reset (RES) instruction is used to reset (0) the counter.
Using the CTU and CTD Instructions
Counter instructions use the following parameters:
•
Counter - This is the address of the counter within the data file. All
counters are 3-word data elements. Word 0 contains the Control and
Status Bits, Word 1 contains the Preset, and Word 2 contains the
Accumulated Value.
CU = Count Up Enable Bit
CD = Count Down Enable Bit
DN = Count Done Bit
OV = Count Overflow Bit
UN = Count Underflow Bit
•
Preset - When the accumulator reaches this value, the DN bit is set.
The preset data range is from -32768 to 32767.
•
Accumulator - The accumulator contains the current count. The
accumulator data range is from -32768 to 32767.
The accumulated value is incremented (CTU) or decremented (CTD)
on each false-to-true rung transition. The accumulated value is
retained when the rung condition again becomes false, and when
power is cycled on the controller. The accumulated count is
Word
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Word 0
CU CD DN OV UN Not Used
Word 1
Preset Value
Word 2
Accumulated Value
-32,768
+32,767
0
Overflow
Underflow
Counter Accumulator Value