Publication 1763-RM001C-EN-P - October 2009
Sequencer Instructions
247
•
Source - The source operand is a constant or address of the value
used to fill the currently available position sequencer file. The
address level of the source must match the sequencer file. If file is a
word type, then source must be a word type. If file is a long word
type, then source must be a long word type. The data range for the
source is from -32,768 to 32,767 (word) or -2,147,483,648 to
2,147,483,647 (long word).
•
Control - This is a control file address. The status bits, stack length,
and the position value are stored in this element. The control
element consists of 3 words:
•
Length - The length operand contains the number of steps in the
sequencer file (this is also the length of source if it is a file data
type). The length of the sequencer can range from 1 to 256.
•
Position - This is the current location or step in the sequencer file
(as well as source if it is a file data type). It determines the next
location in the stack to receive the value or constant found in
source. Position is a component of the control register. The position
can range from 0 to 255.
Addressing Modes and File Types can be used as shown in the following
table:
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Word 0
EN
(1)
(1) EN - Enable Bit is set by a false-to-true rung transition and indicates that the instruction is enabled.
--
DN
(2)
(2) DN - Done Bit is set after the instruction has operated on the last word in the sequencer file. It is reset on the next
false-to-true rung transition after the rung goes false.
--
ER
(3)
(3) ER - Error Bit is set when the controller detects a negative position value, or a negative or zero length value. When the
ER bit is set, the minor error bit (S2:5/2) is also set.
not used
FD
not used
Word 1
Length - contains the index of the last element in the sequencer reference file
Word 2
Position - the current position in the sequence
SQL Instruction Valid Addressing Modes and File Types
For definitions of the terms used in this table see Using the Instruction Descriptions on page 82.
Parameter
Data Files
Function Files
CS - Com
m
s
IOS - I/O
DLS
-
D
a
ta
L
o
g
Address
Mode
(1)
Address Level
O
I
S
B
T,
C
, R
N
F
ST
L
MG, P
D
RI/RIX
PLS
RTC
HSC
PTO, PW
M
STI
EII
BH
I
MMI
LCD
Immedia
te
Dir
e
c
t
Indir
e
ct
Bit
Wo
rd
Long W
o
rd
Ele
m
ent
File
(2)
•
•
•
•
•
•
•
•
•
•
Source
•
•
•
•
•
•
•
•
•
•
•
Control
(3)
•
•
Length
•
•
Position
•
•
(1) See Important note about indirect addressing.
(2) File Direct and File Indirect addressing also applies.
(3) Control file only.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive