Notes: Units DCF057DX-13DYV0 DCF060DX-14DVV0 DCF064DX-14FVW0
SEPR
1,3,5
6.53
6.60
6.59
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
597984
615991
660192
Rated Refrigerant Capacity
P
A
1,3,5 kW
527.4
548.7
587.3
Rated Power Input D
A
kW
181.9
186.0
201.8
Rated EER
DC,A
2.9
2.95
2.91
Declared Refrigerant Capacity P
B
1,3,5 kW
497.6 / 408.6
521.2 / 423.0
557.9 / 457.9
Declared Power Input D
B
kW
122.7 / 96.3
125.6 / 98.3
134.5 / 107.0
Declared EER
DC,B
4.05 / 4.25
4.15 / 4.30
4.15 / 4.28
Declared Refrigerant Capacity P
C
1,3,5 kW
543.2 / 443.2
567.6 / 458.8
608.7 / 497.3
Declared Power Input D
C
kW
102.7 / 80.2
105.0 / 81.9
112.7 / 89.4
Declared EER
DC,C
5.29 / 5.52
5.41 / 5.60
5.40 / 5.56
Declared Refrigerant Capacity P
D
1,3,5 kW
419.3 / 342.0
436.1 / 356.6
466.3 / 381.9
Declared Power Input D
D
kW
42.7 / 52.3
44.6 / 54.2
47.5 / 57.5
Declared EER
DC,D
9.82 / 6.54
9.79 / 6.57
9.82 / 6.64
SSCEE
2,3,5
%
168.0
17%.1
168.0
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
530.1
551.6
590.9
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
527.4
548.7
587.3
Declared EER
d
35°C
2.9
2.95
2.91
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
497.6 / 408.6
521.2 / 423.0
557.9 / 457.9
Declared EER
d
30°C
4.05 / 4.25
4.15 / 4.30
4.15 / 4.28
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
543.2 / 443.2
567.6 / 458.8
608.7 / 497.3
Declared EER
d
25°C
5.29 / 5.52
5.41 / 5.60
5.40 / 5.56
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
419.3 / 342.0
436.1 / 356.6
466.3 / 381.9
Declared EER
d
20°C
9.82 / 6.54
9.79 / 6.57
9.82 / 6.64
Sound Power Level LWA
dB(A)
Air flow rate
m³/h
187085
201476
201476
Off mode P
OFF
kW
0.157
0.157
0.157
Thermostat-off mode P
TO
kW
3.144
3.342
4.167
Standby Mode P
SB
kW
0.296
0.301
0.301
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
Technical Data
Ecodesign
DCF057DX-13DYV0, DCF060DX-14DVV0, DCF064DX-14FVW0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
DeltaChill™ Air Cooled and FreeCool
Introduction
291
Chiller Technical Manual 7267818 V1.13.0_01_2018