Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
133
Chiller Technical Manual 7267818 V1.13.0_01_2018
Fre
eC
oo
l
ELECTRICAL DATA
82
83
84
Unit Data
DCF082TX-18GYYY
DCF085TX-17HYVV
DCF089TX-18HVVV
Nominal Run Amps
(1)
A
523.4
568.0
596.5
Maximum Start Amps
A
799.0
835.4
863.9
Recommended Mains Fuse Size
A
560
630
630
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (EC)
Quantity
18
17
18
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
47.9 / 47.9 / 47.9
47.9 / 55.2 / 55.2
55.2 / 55.2 / 55.2
Quantity
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
Motor Rating
kW
29.8 / 29.8 / 29.8
29.8 / 33.1 / 33.1
33.1 / 33.1 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 326 / 326
326 / 326 / 326
326 / 326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
500.7
531.5
552.7
Reactive power reduction/saving
(4) kVAr
42.8
65.2
76.5
Maximum Start Amps
A
776.3
798.9
820.1
Recommended Mains Fuse Size
A
560
630
630
Electronic Soft-start
Nominal Run Amps
A
523.4
568.0
596.5
Maximum Start Amps
A
668.6
705.0
733.5
Recommended Mains Fuse
A
560
630
630
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
500.7
531.5
552.7
Maximum Start Amps
A
645.9
668.5
689.7
Recommended Mains Fuse Size
A
560
630
630
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
551.5
596.3
624.9
Recommended Mains Fuse Size
A
630
630
670
Motor Rating
kW
16.4
16.4
16.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
35.0
35.0
35.0
Unit Nominal Run Amps
A
558.0
602.8
631.4
Recommended Mains Fuse Size
A
630
630
670
Motor Rating
kW
20.3
20.3
20.3
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
545.5
589.6
617.9
Recommended Mains Fuse Size
A
630
630
670
Motor Rating
kW
16.8
16.8
16.8
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
33.2
33.2
33.2
Unit Nominal Run Amps
A
550.7
594.7
622.9
Recommended Mains Fuse Size
A
630
630
670
Motor Rating
kW
20.7
20.7
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet