DeltaChill™ Air Cooled and FreeCool
152
Chiller Technical Manual 7267818 V1.13.0_01_2018
A
ir C
oo
led
Ambient (°C)
Model
Supply
Temp
°C
25°C
30°C
35°C
40°C
Output
Input
Output
Input
Output
Input
Output
Input
kW
kW
kW
kW
kW
kW
kW
kW
155
DCC060DX-14DVW0
5
620.5
156.2
587.8
172.4
551.7
191.0
512.5
212.0
6
638.5
157.2
604.9
173.5
567.9
192.1
527.6
213.2
7
656.6
158.3
622.3
174.6
584.3
193.3
542.9
214.3
8
675.0
159.4
639.8
175.7
600.8
194.4
558.5
215.5
9
693.5
160.6
657.5
176.9
617.6
195.6
574.2
216.7
10
712.1
161.8
675.3
178.1
634.6
196.8
590.1
218.0
156
DCC063DX-14DWW0
5
659.4
168.1
623.8
185.5
584.9
205.4
542.7
227.8
6
678.2
169.3
641.7
186.7
601.7
206.7
558.4
229.1
7
697.2
170.5
659.8
188.0
618.8
208.0
574.3
230.4
8
716.4
171.8
678.2
189.3
636.0
209.3
590.4
231.8
9
735.8
173.1
696.6
190.6
653.5
210.7
606.8
233.2
10
755.4
174.4
715.3
192.0
671.1
212.1
623.3
234.6
157
DCC066TX-13GPPY
5
693.7
188.1
654.5
207.6
611.7
229.8
565.7
254.4
6
713.4
189.6
673.0
209.2
629.0
231.4
581.8
256.0
7
733.3
191.2
691.8
210.8
646.6
233.0
598.1
257.7
8
753.4
192.7
710.8
212.4
664.4
234.7
614.6
259.4
9
773.7
194.4
730.0
214.1
682.5
236.4
631.4
261.2
10
794.2
196.0
749.4
215.8
700.7
238.1
648.4
262.9
158
DCC070TX-14GPYY
5
732.1
201.6
691.5
222.5
647.1
246.1
599.4
272.4
6
752.9
203.2
711.2
224.1
665.5
247.8
616.4
274.1
7
773.9
204.8
731.1
225.8
684.2
249.5
633.7
275.9
8
795.1
206.4
751.2
227.5
703.1
251.3
651.3
277.7
9
816.5
208.1
771.5
229.2
722.2
253.1
669.1
279.5
10
838.1
209.8
792.0
231.0
741.5
254.9
687.1
281.3
159
DCC055DX-15DYV0
5
572.7
138.8
544.5
153.0
512.7
169.2
478.0
187.6
6
589.7
139.7
560.7
153.9
528.1
170.1
492.4
188.5
7
606.9
140.6
577.1
154.7
543.6
171.0
507.0
189.3
8
624.3
141.5
593.6
155.6
559.3
171.9
521.8
190.2
9
641.8
142.4
610.4
156.5
575.3
172.8
536.8
191.2
10
659.4
143.3
627.3
157.4
591.4
173.7
552.1
192.1
160
DCC059DX-16DVV0
5
601.3
142.2
571.5
156.9
537.7
173.7
500.8
192.9
6
619.5
143.1
588.7
157.7
554.0
174.6
516.1
193.7
7
638.0
144.0
606.2
158.6
570.6
175.4
531.6
194.6
8
656.7
145.0
623.8
159.5
587.3
176.3
547.4
195.5
9
675.2
146.0
641.7
160.4
604.3
177.3
563.4
196.4
10
694.0
146.9
659.7
161.4
621.5
178.2
579.6
197.4
161
DCC061DX-16DVW0
5
629.6
152.9
598.0
168.7
562.6
186.8
523.9
207.3
6
648.2
153.9
615.7
169.6
579.3
187.7
539.6
208.2
7
667.0
154.9
633.5
170.6
596.3
188.7
555.5
209.3
8
685.9
155.9
651.6
171.6
613.4
189.7
571.6
210.3
9
704.9
156.9
669.9
172.6
630.8
190.8
588.0
211.3
10
724.0
158.0
688.3
173.7
648.3
191.8
604.6
212.4
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (comp fans).
3
Duties applicable for chilled water ∆T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x ∆T)
6
For conditions outside of those quoted please refer to Airedale.
DCC Performance Data EC Fans