DeltaChill™ Air Cooled and FreeCool
111
Chiller Technical Manual 7267818 V1.13.0_01_2018
Fre
eC
oo
l
ELECTRICAL DATA
16
17
18
Unit Data
DCF055DR-12DPV0
DCF057DR-12DYY0
DCF058DR-11DYV0
Nominal Run Amps
(1)
A
347.1
348.9
369.2
Maximum Start Amps
A
610.5
624.5
636.6
Recommended Mains Fuse Size
A
400
400
400
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (EC)
Quantity
12
12
11
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 55.2
47.9 / 47.9
47.9 / 55.2
Quantity
2 + 3
3 + 3
3 + 3
Motor Rating
kW
36.2 / 33.1
29.8 / 29.8
29.8 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 326
326 / 326
326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
324.0
333.8
347.3
Reactive power reduction/saving
(4) kVAr
41.2
28.6
39.8
Maximum Start Amps
A
587.4
609.4
614.7
Recommended Mains Fuse Size
A
400
400
400
Electronic Soft-start
Nominal Run Amps
A
347.1
348.9
369.2
Maximum Start Amps
A
480.1
494.1
506.2
Recommended Mains Fuse
A
400
400
400
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
324.0
333.8
347.3
Maximum Start Amps
A
457.0
479.0
484.3
Recommended Mains Fuse Size
A
400.0
400.0
400.0
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
14.8
21.2
21.2
Unit Nominal Run Amps
A
361.8
369.8
390.2
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
8.4
12.1
12.1
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
28.5
28.5
Unit Nominal Run Amps
A
368.2
377.1
397.5
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
12.1
16.4
16.4
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
13.9
19.8
19.8
Unit Nominal Run Amps
A
358.2
365.2
385.3
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
8.6
12.4
12.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
26.9
26.9
Unit Nominal Run Amps
A
363.1
371.1
391.0
Recommended Mains Fuse Size
A
400
400
450
Motor Rating
kW
12.4
16.8
16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet