Chillers
DeltaChill™ Air Cooled and FreeCool
189
Chiller Technical Manual 7267818 V1.13.0_01_2018
A
ir C
oo
led
107
108
109
Unit Data
DCC050DR-12EPV0
DCC052DR-12EYY0
DCC054DR-11DYV0
Nominal Run Amps
(1)
A
347.1
348.9
369.2
Maximum Start Amps
A
610.5
624.5
636.6
Recommended Mains Fuse Size
A
400
400
400
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (EC)
Quantity
12
12
11
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 55.2
47.9 / 47.9
47.9 / 55.2
Quantity
2 + 3
3 + 3
3 + 3
Motor Rating
kW
36.2 / 33.1
29.8 / 29.8
29.8 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 326
326 / 326
326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
324.0
333.8
347.3
Reactive power reduction/saving
(4)
kVAr
41.2
28.6
39.8
Maximum Start Amps
A
587.4
609.4
614.7
Recommended Mains Fuse Size
A
400
400
400
Electronic Soft-start
Nominal Run Amps
A
347.1
348.9
369.2
Maximum Start Amps
A
480.1
494.1
506.2
Recommended Mains Fuse
A
400
400
400
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
324.0
333.8
347.3
Maximum Start Amps
A
457.0
479.0
484.3
Recommended Mains Fuse Size
A
400
400
400
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
8.9
8.9
8.9
Unit Nominal Run Amps
A
355.6
357.3
377.7
Recommended Mains Fuse Size
A
400
400
400
Motor Rating
kW
4.4
4.4
4.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
358.1
359.8
380.2
Recommended Mains Fuse Size
A
400
400
400
Motor Rating
kW
6.1
6.1
6.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
7.3
7.3
7.3
Unit Nominal Run Amps
A
352.9
354.8
375.1
Recommended Mains Fuse Size
A
400
400
400
Motor Rating
kW
4.5
4.5
4.5
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
10.1
10.1
10.1
Unit Nominal Run Amps
A
355.2
357.2
377.4
Recommended Mains Fuse Size
A
400
400
400
Motor Rating
kW
6.3
6.3
6.3
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Regular Quiet