Te
ch
ni
ca
l
Chillers
DeltaChill™ Air Cooled and FreeCool
194
Chiller Technical Manual 7267818 V1.13.0_01_2018
A
ir C
oo
led
122
123
124
Unit Data
DCC080TR-14GYVV
DCC070TR-16GPPY
DCC077TR-15GYYY
Nominal Run Amps
(1)
A
556.4
463.3
511.7
Maximum Start Amps
A
823.8
726.7
787.3
Recommended Mains Fuse Size
A
630
500
560
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (EC)
Quantity
14
16
15
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
47.9 / 55.2 / 55.2
59.2 / 59.2 / 47.9
47.9 / 47.9 / 47.9
Quantity
3 + 3 + 3
2 + 2 + 3
3 + 3 + 3
Motor Rating
kW
29.8 / 33.1 / 33.1
36.2 / 36.2 / 29.8
29.8 / 29.8 / 29.8
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 326 / 326
298 / 298 / 326
326 / 326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
519.8
438.6
489.1
Reactive power reduction/saving
(4)
kVAr
65.2
45.6
42.8
Maximum Start Amps
A
787.2
702.0
764.7
Recommended Mains Fuse Size
A
630
500
560
Electronic Soft-start
Nominal Run Amps
A
556.4
463.3
511.7
Maximum Start Amps
A
693.4
596.3
656.9
Recommended Mains Fuse
A
630
500
560
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
519.8
438.6
489.1
Maximum Start Amps
A
656.8
571.6
634.3
Recommended Mains Fuse Size
A
630
500
560
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
567.5
474.3
522.7
Recommended Mains Fuse Size
A
630
500
560
Motor Rating
kW
6.2
6.2
6.2
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
21.2
Unit Nominal Run Amps
A
577.5
484.3
532.6
Recommended Mains Fuse Size
A
630
560
560
Motor Rating
kW
12.1
12.1
12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
10.2
10.2
10.2
Unit Nominal Run Amps
A
564.6
471.6
520.1
Recommended Mains Fuse Size
A
630
500
560
Motor Rating
kW
6.4
6.4
6.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
19.8
Unit Nominal Run Amps
A
572.3
479.5
528.0
Recommended Mains Fuse Size
A
630
500
560
Motor Rating
kW
12.4
12.4
12.4
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Regular Quiet
Содержание DeltaChill
Страница 1: ...Technical Manual DeltaChill Air Cooled DeltaChill Free Cooling Chiller 500kW 1000kW ...
Страница 300: ...Chillers Introduction DeltaChill Air Cooled and FreeCool 300 Chiller Technical Manual 7267818 V1 13 0_01_2018 Technical ...
Страница 301: ...Chillers DeltaChill Air Cooled and FreeCool Introduction 301 Chiller Technical Manual 7267818 V1 13 0_01_2018 Technical ...