Chillers
DeltaChill™ Air Cooled and FreeCool
106
Chiller Technical Manual 7267818 V1.13.0_01_2018
Te
ch
ni
ca
l
Fr
ee
C
oo
l
DCF Electrical Data - Regular Quiet
ELECTRICAL DATA
1
2
3
Unit Data
DCF046DR-07DXY0
DCF048DR-07DPY0
DCF051DR-08DPV0
Nominal Run Amps
(1)
A
292.9
303.4
331.7
Maximum Start Amps
A
568.5
566.8
595.1
Recommended Mains Fuse Size
A
315
355
355
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (EC)
Quantity
7
7
8
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
36 / 47.9
59.2 / 47.9
59.2 / 55.2
Quantity
3 + 3
2 + 3
2 + 3
Motor Rating
kW
22.7 / 29.8
36.2 / 29.8
36.2 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
210 / 326
298 / 326
298 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
281.1
287.2
308.4
Reactive power reduction/saving
(4) kVAr
22.6
29.8
41.1
Maximum Start Amps
A
556.7
550.6
571.8
Recommended Mains Fuse Size
A
315
355
355
Electronic Soft-start
Nominal Run Amps
A
292.9
303.4
331.7
Maximum Start Amps
A
438.1
436.4
464.7
Recommended Mains Fuse
A
315
355
355
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
281.1
287.2
308.4
Maximum Start Amps
A
426.3
420.2
441.4
Recommended Mains Fuse Size
A
315.0
355.0
355.0
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
14.8
14.8
14.8
Unit Nominal Run Amps
A
307.5
318.0
346.4
Recommended Mains Fuse Size
A
355
355
400
Motor Rating
kW
8.4
8.4
8.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
321.1
331.7
360.1
Recommended Mains Fuse Size
A
355
355
400
Motor Rating
kW
16.4
16.4
16.4
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
13.9
13.9
13.9
Unit Nominal Run Amps
A
304.3
314.7
342.8
Recommended Mains Fuse Size
A
355
355
400
Motor Rating
kW
8.6
8.6
8.6
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
315.2
325.4
353.3
Recommended Mains Fuse Size
A
355
355
400
Motor Rating
kW
16.8
16.8
16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.