Chiller Technical Manual 7267818 V1.13.0_01_2018
Installation Data
Weights, Point Loadings & Centre of Gravity (C of G) DCC
Point loads
L1
L2
L3
L4
L5
L6
L7
R1
R2
R3
R4
R5
R6
R7
C of
G 1
C of
G 2
kg
mm mm
125 DCC080TR-16GYYV
755 700 640 700 540
990 915 840 915 705
960 4315
126 DCC083TR-15GVVV
760 705 645 705 540
1000 925 850 925 710
955 4310
127 DCC086TR-15GVVW 760 705 645 705 540
1010 940 855 940 715
950 4290
128 DCC088TR-15GVWW 580 565 550 530
740 725 705 680
970 3280
129 DCC091TR-15GWWW 595 575 550 520
790 760 725 690
955 3200
130 DCC074TR-17GPYY
540 520 495 520 450
690 660 630 660 575
975 3635
131 DCC079TR-18GYYY
545 520 495 520 450
700 665 635 665 575
970 3625
132 DCC082TR-17GYVV
550 525 495 525 450
710 675 645 675 585
965 3625
133 DCC085TR-18GVVV
550 525 500 525 450
720 690 650 690 590
960 3605
134 DCC088TR-18GVVW 660 620 580 620 520
835 785 730 785 660
975 4155
135 DCC091TR-18GVWW 730 685 635 685 550
920 865 805 865 695
975 4440
136 DCC094TR-18GWWW 755 700 640 700 540
970 900 825 900 695
965 4320
137 DCC082TR-19GYYV
550 520 485 515 520 440 445 715 670 630 670 670 670 475 965 4610
138 DCC084TR-20GYVV
555 520 490 515 520 440 450 715 675 635 675 675 675 480 965 4630
139 DCC087TR-21GVVV
580 550 520 545 550 465 470 750 710 670 710 710 710 495 965 5055
140 DCC090TR-21GVVW 585 550 520 545 550 465 475 760 720 675 720 720 720 505 960 5050
141 DCC093TR-21GVWW 585 555 520 550 555 465 475 765 725 680 725 725 725 505 960 5040
142 DCC096TR-21GWWW 585 555 520 550 555 470 470 775 730 690 730 730 730 510 955 5020
143 DCC048DX-10EPV0
505 495 485 475
695 680 665 650
935 2765
144 DCC049DX-10EYY0
525 505 485 465
745 715 690 660
920 2690
145 DCC049DX-12EPV0
610 585 565 535
825 795 760 725
945 3210
146 DCC051DX-12EYY0
620 595 565 530
840 805 765 720
940 3170
147 DCC053DX-11DYV0
620 595 565 535
850 815 775 730
935 3175
148 DCC056DX-12DVV0
625 600 565 530
870 830 785 735
930 3155
149 DCC058DX-12DVW0
600 585 565 585 530
795 770 745 770 705
955 3750
150 DCC061DX-12DWW0 610 590 575 590 540
825 800 775 800 730
940 3755
151 DCC050DX-14EPV0
680 635 585 635
515
940 875 805 875 710
930 4050
2
1
L1
L2
L3
L4
R1
R2
R3
R4
= C of G
(1) Point load numbering starts from the control panel end of the chiller. Illustration above is for a 8 mount configuration
(2) Point loads indicated are for standard unit only
Содержание DeltaChill
Страница 1: ...Technical Manual DeltaChill Air Cooled DeltaChill Free Cooling Chiller 500kW 1000kW ...
Страница 300: ...Chillers Introduction DeltaChill Air Cooled and FreeCool 300 Chiller Technical Manual 7267818 V1 13 0_01_2018 Technical ...
Страница 301: ...Chillers DeltaChill Air Cooled and FreeCool Introduction 301 Chiller Technical Manual 7267818 V1 13 0_01_2018 Technical ...