Technical Data
Ecodesign
DCC086TR-15GVVW, DCC088TR-15GVWW, DCC091TR-15GWWW
Notes: Units DCC086TR-15GVVW DCC088TR-15GVWW DCC091TR-15GWWW
SEPR
1,3,5
5.47
5.39
5.31
SEPR Tier
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Annual Electricity Consumption
kWh/a
1150226
1204063
1260607
Rated Refrigerant Capacity
P
A
1,3,5 kW
849.2
876.4
903.5
Rated Power Input D
A
kW
304.4
318.7
333.4
Rated EER
DC,A
2.79
2.75
2.71
Declared Refrigerant Capacity P
B
1,3,5 kW
841.3 / 743.9
874.5 / 766.6
907.6 / 799.7
Declared Power Input D
B
kW
216.7 / 187.4
229.7 / 195.3
242.7 / 208.3
Declared EER
DC,B
3.88 / 3.97
3.81 / 3.92
3.74 / 3.84
Declared Refrigerant Capacity P
C
1,3,5 kW
803.3 / 698.6
827.3 / 722.6
861.6 / 746.6
Declared Power Input D
C
kW
156.6 / 131.8
163.2 / 138.5
174.2 / 145.2
Declared EER
DC,C
5.13 / 5.30
5.07 / 5.22
4.95 / 5.14
Declared Refrigerant Capacity P
D
1,3,5 kW
739.0 / 606.8
765.5 / 633.2
791.9 / 659.7
Declared Power Input D
D
kW
112.1 / 91.1
117.6 / 96.6
123.1 / 102.1
Declared EER
DC,D
6.60 / 6.66
6.51 / 6.55
6.44 / 6.46
SSCEE
2,3,5
%
169.5
167.3
164.4
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
851.5
878.9
906.2
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
849.2
876.4
903.5
Declared EER
d
35°C
2.79
2.75
2.71
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
841.3 / 743.9
874.5 / 766.6
907.6 / 799.7
Declared EER
d
30°C
3.88 / 3.97
3.81 / 3.92
3.74 / 3.84
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
803.3 / 698.6
827.3 / 722.6
861.6 / 746.6
Declared EER
d
25°C
5.13 / 5.30
5.07 / 5.22
4.95 / 5.14
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
739.0 / 606.8
765.5 / 633.2
791.9 / 659.7
Declared EER
d
20°C
6.60 / 6.66
6.51 / 6.55
6.44 / 6.46
Sound Power Level LWA
dB(A)
95
95
96
Air flow rate
m³/h
347991
347991
347991
Off mode P
OFF
kW
0.169
0.169
0.169
Thermostat-off mode P
TO
kW
2.970
3.206
3.453
Standby Mode P
SB
kW
0.353
0.353
0.353
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
Introduction
DeltaChill™ Air Cooled and FreeCool
242
Chiller Technical Manual 7267818 V1.13.0_01_2018