background image

BARCODE

EN

Installation and Maintenance Manual

TRANSLATION FROM ORIGINAL 

21.11. 6755517_05

EN

• 

DHW PRODUCTION UP TO 122°F

• 

EXTERNAL AIR TEMPERATURE UP TO 14°F

• 

AVAILABLE VERSION WITH BUILT-IN HYDRONIC KIT

ANL 

60Hz

Technical and Installation manual

60Hz

Содержание ANL

Страница 1: ...and Maintenance Manual TRANSLATION FROM ORIGINAL 21 11 6755517_05 EN DHW PRODUCTION UP TO 122 F EXTERNAL AIR TEMPERATURE UP TO 14 F AVAILABLE VERSION WITH BUILT IN HYDRONIC KIT ANL 60Hz Technical and...

Страница 2: ......

Страница 3: ...st grade materials and with cutting edge technology The quality level is being constantly monitored so AERMEC products are synonymous with Safety Quality and Reliability The data may undergo modificat...

Страница 4: ......

Страница 5: ...BRATION 19 14 SOUND DATA 20 15 GENERAL WARNINGS 21 16 RECEPTION 23 16 1 LIFTING AND HANDLING 23 17 STORAGE 24 18 HYDRAULIC CONNECTIONS 25 19 HYDRAULIC CIRCUITS OF PRINCIPLE 26 19 1 HYDRAULIC CIRCUIT F...

Страница 6: ...utdoor condensed in the air with R410A Series ANL have been designed and manufactured to satisfy heating and cooling needs and the production of domestic hot water DHW in medium to small commercial or...

Страница 7: ...Model H heat pump 8 VERSION standard P with pump A with storage tank and pump 9 HEAT RECOVERY without heat recovery units 10 COILS in aluminium 11 FIELD OF USE standard 1 12 EVAPORATOR standard PED n...

Страница 8: ...transducer HPS High pressure switch LPT Low pressure transducer VIC Cycle reversing valve CN Finned coil CV One way valve F Dehydrator filter AL Liquid storage tank TEV Thermostatic valve BHE Plate e...

Страница 9: ...ers and mechanically by anti intrusion metal grids according to the IEC EN 60335 2 40 Standard 5 3 HYDRAULIC CIRCUIT STANDARD COMPONENTS WATER FILTER Equipped with steel filtering mesh prevents the he...

Страница 10: ...g times of the compressor in systems with low water content Intelligent defrosting for pressure reduction allows to determine when the coil is effectively defrosted avoiding useless defrosting Set poi...

Страница 11: ...NET The device allows the control the management and the remote monitoring of a Chiller with a PC smartphone or tablet using Cloud connection AERNET works as Master while every unit connected is confi...

Страница 12: ...k The combined effects of the salt loaded mist and industrial emissions accelerate corrosion Within the manufacturing plants corrosive gas may result from the processing of chemicals or by the typical...

Страница 13: ...3 HP HA 220V 3 60Hz A 34 45 42 86 HP HA 460V 3 60Hz A 18 76 22 93 Peak current LRA H 220V 3 60Hz A 168 4 193 2 H 460V 3 60Hz A 82 4 95 3 HP HA 220V 3 60Hz A 171 4 198 8 HP HA 460V 3 60Hz A 83 9 98 1 M...

Страница 14: ...fm 8 240 7 946 Input current A 2 2 Input power kW 0 6 0 6 SOUND DATA Sound power dB A 76 0 77 0 Sound pressure 10m 33ft dB A 44 0 45 0 DIMENSION Height in 53 53 Width in 30 30 Depth in 69 69 Weight H...

Страница 15: ...15 5 10 14 5 0 32 5 10 50 15 20 68 25 30 86 35 40 104 45 46 C 114 8 F 46 C 114 8 F 50 122 C F 2 35 6 3 4 5 6 41 7 8 9 10 50 11 12 13 14 15 59 16 17 18 19 20 68 C F EXTERNAL AIR TEMPERATURE TEMPERATURE...

Страница 16: ...Corrective factor of pressure drop PROPYLENE GLYCOL COOLING MODE CORRECTION FACTOR WITH PROPILENE GLYCOL COOLING MODE Freezing Point C 0 3 43 5 30 7 44 9 98 13 08 16 86 21 47 27 04 33 72 Percent PROP...

Страница 17: ...5 80 7 25 8 70 10 15 11 60 0 1000 2000 3000 4000 5000 6000 7000 8000 l h gpm 0 4 9 13 18 22 26 31 35 1 2 1 ANL 100 2 ANL 150 0 2 4 6 8 10 12 14 16 18 20 0 0 0 58 0 29 0 87 1 16 1 45 1 74 2 03 2 32 2 6...

Страница 18: ...40 50 Multiplicative coefficients 1 02 1 0 985 0 97 0 95 0 93 0 91 12 2 1 USEFUL HEADS The static pressures stated here are at net of the pressure drops of the heat exchang ers filter storage tank Th...

Страница 19: ...tem also for glycoled water functioning Values are worked out by multiplying the reference value by the corrective coefficient 13 2 EXPANSION VESSEL CALIBRATION Standard pre load pressure value of exp...

Страница 20: ...tor Q 2 at 10mt 33ft distance from external surface of unit in compliance with ISO 3744 regulations KEY Water input temperature 12 C 53 6 F Temperature of produced water 7 C 44 6 F External air tempe...

Страница 21: ...check for leaks and make any necessary repairs The installation must comply with the requirements of EN378 3 and the local current regulations In particular indoor installation must ensure adequate v...

Страница 22: ...ections of mobile elements are correctly in place before restarting the unit Fans motors and belt drives may be in motion always wait for them to stop and take appropriate precautions to prevent their...

Страница 23: ...asporto e movimentazione accluse al presente manuale Controllare che gli accessori necessari all installazione in loco siano stati consegnati e siano funzionanti Se l unit viene fornita precaricata co...

Страница 24: ...istance Check that the contact surfaces of the anti vibration supports are levelled to the base If necessary use spacers or level the base but in any case make sure that the anti vibration supports re...

Страница 25: ...near the suction of the pump High concentration of glycol could stuck the pump Do not use the pump to mix water and glycol HYDRAULIC CONNECTIONS The units may be available with or without integrated...

Страница 26: ...3 70 300 ppm Chloride ions Cl 50 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Differential pressur...

Страница 27: ...0 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Differential pressure switch 3 Water temperature pr...

Страница 28: ...0 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Water temperature probe 3 Differential pressure swi...

Страница 29: ...AVITY A B C D KIT VT Gy Gx ANL100H 650 381 604 32 2 33 3 17 0 17 5 15 P 690 381 640 31 2 32 2 18 0 18 6 15 A 800 381 640 30 1 30 9 19 2 19 8 15 ANL150H 710 382 630 31 4 32 6 17 7 18 3 15 P 756 382 671...

Страница 30: ...EN 21 11 6755517_05 30 22 MINIMUM TECHNICAL SPACES A1 C1 B2 C2 B1 ANL 100 150 A1 in 118 2 118 2 B1 in 31 5 31 5 B2 in 43 3 43 3 C1 in 31 5 31 5 C2 in 31 5 31 5...

Страница 31: ...ance earth connection For units with three phase power supply check the correct connection of the phases ATTENTION All the electrical operations must be carried out by personnel in possession of the n...

Страница 32: ...rator pressure drop tables present in this manual Check the correct functioning of the flow meters if installed Closing the cut off valve at the output of the heat exchanger the unit control panel mus...

Страница 33: ...tions to prevent their activation before accessing them Isolate the unit from the mains by means of the external isolator provided for the insertion of padlocks up to 3 for blocking in open position P...

Страница 34: ...ust be replaced after draining the refrigerant gas contained in the circuit During venting protect yourself against any leakage of fluids at dan gerous temperatures and or pressures Always use appropr...

Страница 35: ...tor to near the machine cooling circuit Access the machines and acquire the measurements keeping AWAY from the under pressure parts of the cooling circuit As soon as the measurements are taken turn of...

Страница 36: ...cular attention to under pres sure containers In this case replace them of intervene with specific products General cleaning of the unit Bleed the hydraulic circuit and the heat exchangers the simulta...

Страница 37: ...proper functioning of the thermostatic valve Check the charge of refrigerant gas 1 Check the proper functioning of the solenoid valves MAINTENANCE LIST OF THE RECOMMENDED PERIODIC INTERVENTIONS DECOMM...

Страница 38: ...lth from uncontrolled disposal of Waste Electrical and Electronic Equipment WEEE please return the device using appropriate collection systems or contact the retailer where the product was purchased P...

Страница 39: ......

Страница 40: ...C S p A Via Roma 996 37040 Bevilacqua VR Italia Tel 39 0442 633111 Fax 39 0442 93577 marketing aermec com www aermec com Aermec reserves the right to make all modification deemed necessary for improvi...