18.  HYDRAULIC CONNECTIONS

HYDRAULIC CONNECTIONS

The units may be available with or without integrated hydronic kit, in any 

case:

ATTENTION The choice and installation of components external to the 

unit is up to the installer, who must operate according to the rules of 

good technical design and in compliance with the regulations in force 

in the country of destination.

ATTENTION The hydraulic connection pipes to the unit must be suitably 

dimensioned for the effective water flow rate requested by the system 

when running. The water flow rate to the heat exchanger must always 

be constant

ATTENTION Wash the system thoroughly before connecting the unit. 

This cleaning will eliminate any residues such as welding drips, scale, 

rust, or other impurities from the piping. These substances can also 

deposit inside and cause unit malfunctions.  The connection piping 

must be adequately supported so that its weight does not rest on the 

appliance 

CONNECTIONS

Before starting the system, check that the hydraulic circuits are connected 

to the current exchangers (or, that the evaporator in the air/water units 

or evaporator and condenser in the water water units or the intake and 

flow fittings have not been reversed). The water circulation pump must 

preferably be installed upstream so that the evaporator/condenser is 

subject to a positive pressure. The water inlet and outlet connections are 

indicated in the dimension tables in this manual, or available on www.

aermec.com

It is important to follow the recommendations (not complete) below:

•   The water pipes must not transmit radial or axial forces or vibrations 

to the exchangers (use flexible hoses to reduce the transmitted 

vibrations)

•   It is necessary to install manual or automatic vent valves in the 

highest points of the circuit; and also provide discharge fittings in the 

lowest points to allow emptying the entire circuit

•   To maintain the pressure in the circuits, you must install an expansion 

tank and a safety valve

•   Respect the water inlet and outlet connections shown on the unit

•  Install manometer

 

on the water inlet and outlet fittings.

•   Install stop valve near the water inlet and outlet fittings.

•   After performing a leak test, insulate the pipes to reduce heat loss 

and prevent the formation of condensation

•   If the external water pipes are in an area where it is likely that the 

environment temperature drops below 32°F, insulate the pipes and 

provide an electric heater. As an option, you can also protect the 

pipes inside the unit.

•   Check the continuity of the earthing.

ATTENTION You must install the water filter supplied, in the hydraulic 

circuit upstream of the heat exchanger. FAILURE TO DO THIS 

INVALIDATES THE WARRANTY.

ATTENTION The charge or discharge of the heat exchange fluids must 

be made during installation by qualified technicians using the fittings 

provided on the hydraulic circuit. Never use the unit heat exchangers to 

top-up the heat exchanger fluid.

DISCHARGING SYSTEM

In the event the system is stopped during winter, the water in the heat 

exchanger can freeze damaging the heat exchanger irreversibly. To 

prevent danger of freezing, three solutions are possible:

1.   Full water discharge from the unit.

2.   Using the resistances. In this case the resistances must always be 

supplied with electrical power for the entire period of possible 

freezing (machine in stand-by).

3.   Operation with glycol/water fluid, with a percentage of glycol based 

on the minimum outdoor temperature expected.

ANTI-FREEZE PROTECTION

ATTENTION: the addition of glycol is the only effective protection 

against freezing; the glycol/water solution must be sufficiently 

concentrated to ensure proper protection and prevent ice forming 

at minimum temperature provided for a given installation. Take the 

necessary precautions if using non-passivated anti-freeze solutions 

(monoethylene glycol or monopropylene glycol). Corrosion phenomena 

may occur with these anti-freeze solutions in contact with oxygen.

However, always refer to the glycol supplier documentation to check its 

recommended concentration.

Do not fill up the hydraulic system by glycol near the suction of 

the pump. High concentration of glycol could stuck the pump. 

Do not use the pump to mix water and glycol

HYDRAULIC CONNECTIONS

The units may be available with or without integrated hydronic kit, in any 

case:

ATTENTION The choice and installation of components external to the 

unit is up to the installer, who must operate according to the rules of 

good technical design and in compliance with the regulations in force 

in the country of destination.

ATTENTION The hydraulic connection pipes to the unit must be suitably 

dimensioned for the effective water flow rate requested by the system 

when running. The water flow rate to the heat exchanger must always 

be constant

ATTENTION Wash the system thoroughly before connecting the unit. 

This cleaning will eliminate any residues such as welding drips, scale, 

rust, or other impurities from the piping. These substances can also 

deposit inside and cause unit malfunctions.  The connection piping 

must be adequately supported so that its weight does not rest on the 

appliance 

CONNECTIONS

Before starting the system, check that the hydraulic circuits are connected 

to the current exchangers (or, that the evaporator in the air/water units 

or evaporator and condenser in the water water units or the intake and 

flow fittings have not been reversed). The water circulation pump must 

preferably be installed upstream so that the evaporator/condenser is 

subject to a positive pressure. The water inlet and outlet connections are 

indicated in the dimension tables in this manual, or available on www.

aermec.com

It is important to follow the recommendations (not complete) below:

•   The water pipes must not transmit radial or axial forces or vibrations 

to the exchangers (use flexible hoses to reduce the transmitted 

vibrations)

•   It is necessary to install manual or automatic vent valves in the 

highest points of the circuit; and also provide discharge fittings in the 

lowest points to allow emptying the entire circuit

•   To maintain the pressure in the circuits, you must install an expansion 

tank and a safety valve

•   Respect the water inlet and outlet connections shown on the unit

•  Install manometer

 

on the water inlet and outlet fittings.

•   Install stop valve near the water inlet and outlet fittings.

•   After performing a leak test, insulate the pipes to reduce heat loss 

and prevent the formation of condensation

•   If the external water pipes are in an area where it is likely that the 

environment temperature drops below 32°F, insulate the pipes and 

provide an electric heater. As an option, you can also protect the 

pipes inside the unit.

•   Check the continuity of the earthing.

ATTENTION You must install the water filter supplied, in the hydraulic 

circuit upstream of the heat exchanger. FAILURE TO DO THIS 

INVALIDATES THE WARRANTY.

ATTENTION The charge or discharge of the heat exchange fluids must 

be made during installation by qualified technicians using the fittings 

provided on the hydraulic circuit. Never use the unit heat exchangers to 

top-up the heat exchanger fluid.

DISCHARGING SYSTEM

In the event the system is stopped during winter, the water in the heat 

exchanger can freeze damaging the heat exchanger irreversibly. To 

prevent danger of freezing, three solutions are possible:

1.   Full water discharge from the unit.

2.   Using the resistances. In this case the resistances must always be 

supplied with electrical power for the entire period of possible 

freezing (machine in stand-by).

3.   Operation with glycol/water fluid, with a percentage of glycol based 

on the minimum outdoor temperature expected.

ANTI-FREEZE PROTECTION

ATTENTION: the addition of glycol is the only effective protection 

against freezing; the glycol/water solution must be sufficiently 

concentrated to ensure proper protection and prevent ice forming 

at minimum temperature provided for a given installation. Take the 

necessary precautions if using non-passivated anti-freeze solutions 

(monoethylene glycol or monopropylene glycol). Corrosion phenomena 

may occur with these anti-freeze solutions in contact with oxygen.

However, always refer to the glycol supplier documentation to check its 

recommended concentration.

Do not fill up the hydraulic system by glycol near the suction of 

the pump. High concentration of glycol could stuck the pump. 

Do not use the pump to mix water and glycol

Содержание ANL

Страница 1: ...and Maintenance Manual TRANSLATION FROM ORIGINAL 21 11 6755517_05 EN DHW PRODUCTION UP TO 122 F EXTERNAL AIR TEMPERATURE UP TO 14 F AVAILABLE VERSION WITH BUILT IN HYDRONIC KIT ANL 60Hz Technical and...

Страница 2: ......

Страница 3: ...st grade materials and with cutting edge technology The quality level is being constantly monitored so AERMEC products are synonymous with Safety Quality and Reliability The data may undergo modificat...

Страница 4: ......

Страница 5: ...BRATION 19 14 SOUND DATA 20 15 GENERAL WARNINGS 21 16 RECEPTION 23 16 1 LIFTING AND HANDLING 23 17 STORAGE 24 18 HYDRAULIC CONNECTIONS 25 19 HYDRAULIC CIRCUITS OF PRINCIPLE 26 19 1 HYDRAULIC CIRCUIT F...

Страница 6: ...utdoor condensed in the air with R410A Series ANL have been designed and manufactured to satisfy heating and cooling needs and the production of domestic hot water DHW in medium to small commercial or...

Страница 7: ...Model H heat pump 8 VERSION standard P with pump A with storage tank and pump 9 HEAT RECOVERY without heat recovery units 10 COILS in aluminium 11 FIELD OF USE standard 1 12 EVAPORATOR standard PED n...

Страница 8: ...transducer HPS High pressure switch LPT Low pressure transducer VIC Cycle reversing valve CN Finned coil CV One way valve F Dehydrator filter AL Liquid storage tank TEV Thermostatic valve BHE Plate e...

Страница 9: ...ers and mechanically by anti intrusion metal grids according to the IEC EN 60335 2 40 Standard 5 3 HYDRAULIC CIRCUIT STANDARD COMPONENTS WATER FILTER Equipped with steel filtering mesh prevents the he...

Страница 10: ...g times of the compressor in systems with low water content Intelligent defrosting for pressure reduction allows to determine when the coil is effectively defrosted avoiding useless defrosting Set poi...

Страница 11: ...NET The device allows the control the management and the remote monitoring of a Chiller with a PC smartphone or tablet using Cloud connection AERNET works as Master while every unit connected is confi...

Страница 12: ...k The combined effects of the salt loaded mist and industrial emissions accelerate corrosion Within the manufacturing plants corrosive gas may result from the processing of chemicals or by the typical...

Страница 13: ...3 HP HA 220V 3 60Hz A 34 45 42 86 HP HA 460V 3 60Hz A 18 76 22 93 Peak current LRA H 220V 3 60Hz A 168 4 193 2 H 460V 3 60Hz A 82 4 95 3 HP HA 220V 3 60Hz A 171 4 198 8 HP HA 460V 3 60Hz A 83 9 98 1 M...

Страница 14: ...fm 8 240 7 946 Input current A 2 2 Input power kW 0 6 0 6 SOUND DATA Sound power dB A 76 0 77 0 Sound pressure 10m 33ft dB A 44 0 45 0 DIMENSION Height in 53 53 Width in 30 30 Depth in 69 69 Weight H...

Страница 15: ...15 5 10 14 5 0 32 5 10 50 15 20 68 25 30 86 35 40 104 45 46 C 114 8 F 46 C 114 8 F 50 122 C F 2 35 6 3 4 5 6 41 7 8 9 10 50 11 12 13 14 15 59 16 17 18 19 20 68 C F EXTERNAL AIR TEMPERATURE TEMPERATURE...

Страница 16: ...Corrective factor of pressure drop PROPYLENE GLYCOL COOLING MODE CORRECTION FACTOR WITH PROPILENE GLYCOL COOLING MODE Freezing Point C 0 3 43 5 30 7 44 9 98 13 08 16 86 21 47 27 04 33 72 Percent PROP...

Страница 17: ...5 80 7 25 8 70 10 15 11 60 0 1000 2000 3000 4000 5000 6000 7000 8000 l h gpm 0 4 9 13 18 22 26 31 35 1 2 1 ANL 100 2 ANL 150 0 2 4 6 8 10 12 14 16 18 20 0 0 0 58 0 29 0 87 1 16 1 45 1 74 2 03 2 32 2 6...

Страница 18: ...40 50 Multiplicative coefficients 1 02 1 0 985 0 97 0 95 0 93 0 91 12 2 1 USEFUL HEADS The static pressures stated here are at net of the pressure drops of the heat exchang ers filter storage tank Th...

Страница 19: ...tem also for glycoled water functioning Values are worked out by multiplying the reference value by the corrective coefficient 13 2 EXPANSION VESSEL CALIBRATION Standard pre load pressure value of exp...

Страница 20: ...tor Q 2 at 10mt 33ft distance from external surface of unit in compliance with ISO 3744 regulations KEY Water input temperature 12 C 53 6 F Temperature of produced water 7 C 44 6 F External air tempe...

Страница 21: ...check for leaks and make any necessary repairs The installation must comply with the requirements of EN378 3 and the local current regulations In particular indoor installation must ensure adequate v...

Страница 22: ...ections of mobile elements are correctly in place before restarting the unit Fans motors and belt drives may be in motion always wait for them to stop and take appropriate precautions to prevent their...

Страница 23: ...asporto e movimentazione accluse al presente manuale Controllare che gli accessori necessari all installazione in loco siano stati consegnati e siano funzionanti Se l unit viene fornita precaricata co...

Страница 24: ...istance Check that the contact surfaces of the anti vibration supports are levelled to the base If necessary use spacers or level the base but in any case make sure that the anti vibration supports re...

Страница 25: ...near the suction of the pump High concentration of glycol could stuck the pump Do not use the pump to mix water and glycol HYDRAULIC CONNECTIONS The units may be available with or without integrated...

Страница 26: ...3 70 300 ppm Chloride ions Cl 50 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Differential pressur...

Страница 27: ...0 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Differential pressure switch 3 Water temperature pr...

Страница 28: ...0 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Water temperature probe 3 Differential pressure swi...

Страница 29: ...AVITY A B C D KIT VT Gy Gx ANL100H 650 381 604 32 2 33 3 17 0 17 5 15 P 690 381 640 31 2 32 2 18 0 18 6 15 A 800 381 640 30 1 30 9 19 2 19 8 15 ANL150H 710 382 630 31 4 32 6 17 7 18 3 15 P 756 382 671...

Страница 30: ...EN 21 11 6755517_05 30 22 MINIMUM TECHNICAL SPACES A1 C1 B2 C2 B1 ANL 100 150 A1 in 118 2 118 2 B1 in 31 5 31 5 B2 in 43 3 43 3 C1 in 31 5 31 5 C2 in 31 5 31 5...

Страница 31: ...ance earth connection For units with three phase power supply check the correct connection of the phases ATTENTION All the electrical operations must be carried out by personnel in possession of the n...

Страница 32: ...rator pressure drop tables present in this manual Check the correct functioning of the flow meters if installed Closing the cut off valve at the output of the heat exchanger the unit control panel mus...

Страница 33: ...tions to prevent their activation before accessing them Isolate the unit from the mains by means of the external isolator provided for the insertion of padlocks up to 3 for blocking in open position P...

Страница 34: ...ust be replaced after draining the refrigerant gas contained in the circuit During venting protect yourself against any leakage of fluids at dan gerous temperatures and or pressures Always use appropr...

Страница 35: ...tor to near the machine cooling circuit Access the machines and acquire the measurements keeping AWAY from the under pressure parts of the cooling circuit As soon as the measurements are taken turn of...

Страница 36: ...cular attention to under pres sure containers In this case replace them of intervene with specific products General cleaning of the unit Bleed the hydraulic circuit and the heat exchangers the simulta...

Страница 37: ...proper functioning of the thermostatic valve Check the charge of refrigerant gas 1 Check the proper functioning of the solenoid valves MAINTENANCE LIST OF THE RECOMMENDED PERIODIC INTERVENTIONS DECOMM...

Страница 38: ...lth from uncontrolled disposal of Waste Electrical and Electronic Equipment WEEE please return the device using appropriate collection systems or contact the retailer where the product was purchased P...

Страница 39: ......

Страница 40: ...C S p A Via Roma 996 37040 Bevilacqua VR Italia Tel 39 0442 633111 Fax 39 0442 93577 marketing aermec com www aermec com Aermec reserves the right to make all modification deemed necessary for improvi...

Отзывы: