MODUCONTROL
CONTROL PANEL
5.6. ELECTRIC COMPONENTS
Electric Control Board
Contains the power section and the management of
controls and safety devices. It is in compliance with
the IEC 60204-1 Standard and the Directives regard
-
ing electromagnetic compatibility EMC 89/336/EEC
and 92/31/EEC.
Door-lock isolating switch
The electric control board can be accessed by re-
moving the voltage. Act on the opening lever of the
control board itself. This lever can be locked using
one or more padlocks during maintenance interven-
tions to prevent the machine being powered up
accidentally.
Control board
Allows complete control of the appliance.
For a more in-depth description please refer to
the user manual.
−
compressors magnet circuit-breaker pro-
tection.
− fans magnet-circuit breakers protection;
− auxiliary magnet circuit-breaker protection
− Heat exchanger inlet/outlet water temper
-
ature probes
−
Gas temperature probe one on the for
pressing line and coil
−
External air temperature probe
►
For further information please refer to user
manual
Electric Regolation
MODU CONTROL
Temperature control of the output water with proportional-integral
algorithm: maintains average output temperature at value set
- Self-adapting differential switch: guarantees minimum functioning
times of the compressor in systems with low water content.
- Intelligent defrosting for pressure reduction: allows to determine
when the coil is effectively defrosted, avoiding useless defrosting
- Set-point compensation with external temperature: reduces energy
consumption
- Pre-alarms with automatic reset: in the case of alarm, a certain
number of re-starts are allowed before the definitive block
alarm on the ∆T: to identify wiring errors (reverse rotation) or
blocked cycle reversing valve
- Compressor functioning hours count.
- Compressor peak count.
- Historical alarms
- Autostart after voltage drop.
- Local or remote control
Display of the start of the unit:
1.
Voltage presence
2.
compressor ON/OFF
3.
functioning mode (hot/cold)
4.
alarm active
Probes, transducers and parameters display
1.
Water outlet
2.
water inlet
3.
Coil temperature (heat pumps)
4.
Pressing gas temperature
5.
External air temperature (heat pumps)
6.
Pressure delivery (heat pumps)
7.
Intake pressure (heat pumps)
8.
Temperature error (sum of the proportional and integral error)
9.
Stand-by times for start-up/switch-off of the compressor
10. Alarms management:
11. Low pressure
12. High pressure (primary alarm: switch directly blocks supply to
compressor)
13. High discharge temperature
14.
Anti-freeze
15.
Water differential flow switch. Alarm on the ∆T
− Alarms with automatic reset with limited number of re-starts be
-
fore blocking.
− ON/OFF external contact
−
Change season from external contact
For further information please refer to user manual.