5.  DESCRIPTION OF COMPONENTS

5.1.  CHILLER CIRCUIT

SCROLL COMPRESSORS 

High efficiency scroll-type hermetic compressors, assembled on elastic antivibra

-

tion supports, driven by a 2-pole electric motor with internal thermal protection. 
of the electric heater casing included as standard. The heater is automatically 

powered when the unit stops, provided that the unit is kept under tension.

WATER SIDE HEAT EXCHANGER

Of the plate-type (AISI 316), externally insulated with closed cell material to 
reduce thermal dispersion. Fitted, as standard, with antifreeze heater.

5.1.1.  WATER FEATURES

SOURCE SIDE HEAT EXCHANGER

Made with copper pipes and aluminium louvered  fins blocked by mecha-

nical expansion of the pipes. Provided with protective grid.

DEHYDRATOR FILTER

Hermetic-mechanical with cartridges made of ceramic and hygroscopic 

material, able to withhold impurities and any traces of humidity present 

in the cooling circuit.

ONE WAY VALVES

Allow one-way flow of the fluid.

THERMOSTATIC VALVE

The mechanical valve, with external equaliser positioned at the evapora-

tor inlet, modulates the flow of gas to the evaporator, according to the 

heat load, in order to ensure a correct heating level of the intake gas.

SOLENOID VALVE

The valve closes when the compressor turns off, preventing the flow of 

refrigerant gas towards the evaporator.

INDICATOR FOR LIQUID PASSAGE WITH HUMIDITY PRESENCE 

SIGNAL

Used to check the refrigerant gas load and the eventual presence of 

humidity in the cooling circuit.

4-WAY CYCLE REVERSE VALVE

Inverts the flow of refrigerant gas.

ONE-WAY VALVES

Allows the passage of the refrigerant in just one direction.

LIQUID STORAGE TANK

Compensates the difference in volume between louveres coil and plate 

exchanger, withholding excess liquid.

5.2.  FRAME AND FANS

SUPPORT FRAME

Load-bearing structure Made of hot-galvanised steel sheet of a suitable 

thickness, varnished with polyester

powders able to resist atmospheric agents over time.

VENTILATION UNIT

Axial fan, balanced statically and dynamically. The electric fans are 

protected electrically by magnet-circuit breakers and mechanically by 

anti-intrusion metal grids, according to the IEC EN 60335-2-40 Standard.

5.3.  HYDRAULIC CIRCUIT STANDARD COMPONENTS

WATER FILTER

Equipped with steel filtering mesh; prevents the heat exchangers from 

clogging.

It is indispensable in order to prevent serious damage to the plate 

exchanger.

DIFFERENTIAL PRESSURE SWITCH

It checks that here is water circulation inside the heat exchangers. Adver-

sary, it blocks the unit.

SAFETY VALVE

Equipped with a piped discharger and intervenes by discharges the over 

pressure in case of anomalous pressures.

AIR VENT

Assembled on the upper part of the hydraulic system; it releases any air 

bubbles that may be present in the system.

5.4.  HYDRAULIC COMPONENTS FOR CONFIGURABLE VERSIONS

CIRCULATION PUMP

Depending on the characteristics of the pump chosen, it offers a useful 

head to overcome the pressure drops in the system.

EXPANSION TANK

With nitrogen pre-load membrane.

SAFETY VALVE

Equipped with a piped discharger and intervenes by discharges the over 

pressure in case of anomalous pressures.

STORAGE TANK

In order to reduce the thermal dispersion and eliminate the phenome-

non of the formation of condensation, it is insulated with polyurethane 

material of a suitable thickness.

It is required to reduce the number of peaks of the compressor and to 

even the temperature of water to be sent to the utilities.

5.5.  SAFETY AND CONTROL COMPONENTS

HIGH PRESSURE SWITCH

With fixed calibration, placed on high pressure side of cooling circuit, inhi-

bits functioning of compressor if abnormal work pressure occurs.

HIGH PRESSURE TRANSDUCER

Placed on high pressure side of cooling circuit, signals the work pressure 

to control board, generating a pre-warning in case abnormal pressure 

occurs.

LOW PRESSURE TRANSDUCER

Allows displaying, on the microprocessor board display, the value of the 

compressor's suction pressure (one per circuit) on the low-pressure side 

of the cooling  circuit.

System: Chiller with plate heat exchanger

PH

7.5-9

Electric conductivity

10-500μS/cm

Total hardness

4.5-8.5°dH

Temperature

< 65°C

Oxygen content

< 0.1 ppm

Max. glycol amount

50%

Phosphates (PO4)

< 2ppm

Manganese (Mn)

< 0.05 ppm

Iron (Fe)

< 0.3 ppm

Alkalinity (HCO3)

70 - 300 ppm

Chloride ions (Cl-)

< 50 ppm

Sulphate ions (SO4)

< 50 ppm

Sulphide ion (S)

none

Ammonium ions (NH4)

none

Silica (SiO2)

< 30ppm

Содержание ANL

Страница 1: ...and Maintenance Manual TRANSLATION FROM ORIGINAL 21 11 6755517_05 EN DHW PRODUCTION UP TO 122 F EXTERNAL AIR TEMPERATURE UP TO 14 F AVAILABLE VERSION WITH BUILT IN HYDRONIC KIT ANL 60Hz Technical and...

Страница 2: ......

Страница 3: ...st grade materials and with cutting edge technology The quality level is being constantly monitored so AERMEC products are synonymous with Safety Quality and Reliability The data may undergo modificat...

Страница 4: ......

Страница 5: ...BRATION 19 14 SOUND DATA 20 15 GENERAL WARNINGS 21 16 RECEPTION 23 16 1 LIFTING AND HANDLING 23 17 STORAGE 24 18 HYDRAULIC CONNECTIONS 25 19 HYDRAULIC CIRCUITS OF PRINCIPLE 26 19 1 HYDRAULIC CIRCUIT F...

Страница 6: ...utdoor condensed in the air with R410A Series ANL have been designed and manufactured to satisfy heating and cooling needs and the production of domestic hot water DHW in medium to small commercial or...

Страница 7: ...Model H heat pump 8 VERSION standard P with pump A with storage tank and pump 9 HEAT RECOVERY without heat recovery units 10 COILS in aluminium 11 FIELD OF USE standard 1 12 EVAPORATOR standard PED n...

Страница 8: ...transducer HPS High pressure switch LPT Low pressure transducer VIC Cycle reversing valve CN Finned coil CV One way valve F Dehydrator filter AL Liquid storage tank TEV Thermostatic valve BHE Plate e...

Страница 9: ...ers and mechanically by anti intrusion metal grids according to the IEC EN 60335 2 40 Standard 5 3 HYDRAULIC CIRCUIT STANDARD COMPONENTS WATER FILTER Equipped with steel filtering mesh prevents the he...

Страница 10: ...g times of the compressor in systems with low water content Intelligent defrosting for pressure reduction allows to determine when the coil is effectively defrosted avoiding useless defrosting Set poi...

Страница 11: ...NET The device allows the control the management and the remote monitoring of a Chiller with a PC smartphone or tablet using Cloud connection AERNET works as Master while every unit connected is confi...

Страница 12: ...k The combined effects of the salt loaded mist and industrial emissions accelerate corrosion Within the manufacturing plants corrosive gas may result from the processing of chemicals or by the typical...

Страница 13: ...3 HP HA 220V 3 60Hz A 34 45 42 86 HP HA 460V 3 60Hz A 18 76 22 93 Peak current LRA H 220V 3 60Hz A 168 4 193 2 H 460V 3 60Hz A 82 4 95 3 HP HA 220V 3 60Hz A 171 4 198 8 HP HA 460V 3 60Hz A 83 9 98 1 M...

Страница 14: ...fm 8 240 7 946 Input current A 2 2 Input power kW 0 6 0 6 SOUND DATA Sound power dB A 76 0 77 0 Sound pressure 10m 33ft dB A 44 0 45 0 DIMENSION Height in 53 53 Width in 30 30 Depth in 69 69 Weight H...

Страница 15: ...15 5 10 14 5 0 32 5 10 50 15 20 68 25 30 86 35 40 104 45 46 C 114 8 F 46 C 114 8 F 50 122 C F 2 35 6 3 4 5 6 41 7 8 9 10 50 11 12 13 14 15 59 16 17 18 19 20 68 C F EXTERNAL AIR TEMPERATURE TEMPERATURE...

Страница 16: ...Corrective factor of pressure drop PROPYLENE GLYCOL COOLING MODE CORRECTION FACTOR WITH PROPILENE GLYCOL COOLING MODE Freezing Point C 0 3 43 5 30 7 44 9 98 13 08 16 86 21 47 27 04 33 72 Percent PROP...

Страница 17: ...5 80 7 25 8 70 10 15 11 60 0 1000 2000 3000 4000 5000 6000 7000 8000 l h gpm 0 4 9 13 18 22 26 31 35 1 2 1 ANL 100 2 ANL 150 0 2 4 6 8 10 12 14 16 18 20 0 0 0 58 0 29 0 87 1 16 1 45 1 74 2 03 2 32 2 6...

Страница 18: ...40 50 Multiplicative coefficients 1 02 1 0 985 0 97 0 95 0 93 0 91 12 2 1 USEFUL HEADS The static pressures stated here are at net of the pressure drops of the heat exchang ers filter storage tank Th...

Страница 19: ...tem also for glycoled water functioning Values are worked out by multiplying the reference value by the corrective coefficient 13 2 EXPANSION VESSEL CALIBRATION Standard pre load pressure value of exp...

Страница 20: ...tor Q 2 at 10mt 33ft distance from external surface of unit in compliance with ISO 3744 regulations KEY Water input temperature 12 C 53 6 F Temperature of produced water 7 C 44 6 F External air tempe...

Страница 21: ...check for leaks and make any necessary repairs The installation must comply with the requirements of EN378 3 and the local current regulations In particular indoor installation must ensure adequate v...

Страница 22: ...ections of mobile elements are correctly in place before restarting the unit Fans motors and belt drives may be in motion always wait for them to stop and take appropriate precautions to prevent their...

Страница 23: ...asporto e movimentazione accluse al presente manuale Controllare che gli accessori necessari all installazione in loco siano stati consegnati e siano funzionanti Se l unit viene fornita precaricata co...

Страница 24: ...istance Check that the contact surfaces of the anti vibration supports are levelled to the base If necessary use spacers or level the base but in any case make sure that the anti vibration supports re...

Страница 25: ...near the suction of the pump High concentration of glycol could stuck the pump Do not use the pump to mix water and glycol HYDRAULIC CONNECTIONS The units may be available with or without integrated...

Страница 26: ...3 70 300 ppm Chloride ions Cl 50 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Differential pressur...

Страница 27: ...0 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Differential pressure switch 3 Water temperature pr...

Страница 28: ...0 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Water temperature probe 3 Differential pressure swi...

Страница 29: ...AVITY A B C D KIT VT Gy Gx ANL100H 650 381 604 32 2 33 3 17 0 17 5 15 P 690 381 640 31 2 32 2 18 0 18 6 15 A 800 381 640 30 1 30 9 19 2 19 8 15 ANL150H 710 382 630 31 4 32 6 17 7 18 3 15 P 756 382 671...

Страница 30: ...EN 21 11 6755517_05 30 22 MINIMUM TECHNICAL SPACES A1 C1 B2 C2 B1 ANL 100 150 A1 in 118 2 118 2 B1 in 31 5 31 5 B2 in 43 3 43 3 C1 in 31 5 31 5 C2 in 31 5 31 5...

Страница 31: ...ance earth connection For units with three phase power supply check the correct connection of the phases ATTENTION All the electrical operations must be carried out by personnel in possession of the n...

Страница 32: ...rator pressure drop tables present in this manual Check the correct functioning of the flow meters if installed Closing the cut off valve at the output of the heat exchanger the unit control panel mus...

Страница 33: ...tions to prevent their activation before accessing them Isolate the unit from the mains by means of the external isolator provided for the insertion of padlocks up to 3 for blocking in open position P...

Страница 34: ...ust be replaced after draining the refrigerant gas contained in the circuit During venting protect yourself against any leakage of fluids at dan gerous temperatures and or pressures Always use appropr...

Страница 35: ...tor to near the machine cooling circuit Access the machines and acquire the measurements keeping AWAY from the under pressure parts of the cooling circuit As soon as the measurements are taken turn of...

Страница 36: ...cular attention to under pres sure containers In this case replace them of intervene with specific products General cleaning of the unit Bleed the hydraulic circuit and the heat exchangers the simulta...

Страница 37: ...proper functioning of the thermostatic valve Check the charge of refrigerant gas 1 Check the proper functioning of the solenoid valves MAINTENANCE LIST OF THE RECOMMENDED PERIODIC INTERVENTIONS DECOMM...

Страница 38: ...lth from uncontrolled disposal of Waste Electrical and Electronic Equipment WEEE please return the device using appropriate collection systems or contact the retailer where the product was purchased P...

Страница 39: ......

Страница 40: ...C S p A Via Roma 996 37040 Bevilacqua VR Italia Tel 39 0442 633111 Fax 39 0442 93577 marketing aermec com www aermec com Aermec reserves the right to make all modification deemed necessary for improvi...

Отзывы: