Chillers
DeltaChill™ Air Cooled and FreeCool
100
Chiller Technical Manual 7267818 V1.13.0_01_2018
Te
ch
ni
ca
l
Fr
ee
C
oo
l
82
83
84
DCF082TX-18GYYY
DCF085TX-17HYVV
DCF089TX-18HVVV
FreeCooling
Yes
Yes
Yes
Enhance Capital Allowance
No
No
No
Number of Refrigeration Circuits
3
3
3
Cooling Duty - EC Fans
Nominal Output - Mechanical
(1) kW
814.8
832.8
872.0
Nominal Input - Mechanical
kW
267.3
285.6
289.7
EER
(2)
3.05
2.92
3.01
ESEER
4.07
4.03
4.12
Nominal Output - Free Cooling
kW
653.3
631.7
666.6
Ambient temperature for
100% Free Cooling
(5) °C
0.0
-0.9
-0.7
Capacity Steps
%
10-25-35-50-60-
70-80-90-100
10-25-35-45-60-
70-80-90-100
10-25-35-50-60-
70-80-90-100
Minimum Turndown Ratio
0.12
0.12
0.12
Dimensions (H x W x L)
mm
2682 x 2200 x 10506
2682 x 2200 x 10506
2682 x 2200 x 10506
Weight
Machine
(3) kg
8580
8635
8780
Operating
kg
10130
10295
10450
Water Volume (Total Internal)
l
1550
1660
1670
Maximum Waterflow
l/s
46.1
63.4
63.4
Minimum Waterflow
l/s
17.7
24.0
24.0
Face Area (Total)
m²
2.38
2.38
2.38
Nominal Airflow - EC Fans
m³/s
72.0
68.0
72.0
Quantity
18
17
18
Maximum Speed - EC Fans
rpm
725
725
725
Compressor
Trio + Trio + Trio
Trio + Trio + Trio
Trio + Trio + Trio
Quantity of Compressors
9
9
9
Oil Charge Volume (Total)
l
3 x 5.3 + 3 x 5.3
+ 3 x 5.3
3 x 5.3 + 3 x 5.3
+ 3 x 5.3
3 x 5.3 + 3 x 5.3
+ 3 x 5.3
Refrigeration
R410A / 2088
Charge (Total)
kg
35 + 37 + 38
35 + 40 + 41
40 + 42 + 43
GWP Tonnes Equivalent CO
2
tCO2
73 + 77 + 79
73 + 84 + 86
84 + 88 + 90
Refrigerant Control
Electronic Expansion Valve (EEV)
Water Inlet / Outlet - Unit
DN150
DN150
DN150
Water Drain / Bleed - Evap
inch
1/2
1/2
1/2
Water System
Minimum System Water Volume
(4)
l
1794
1777
1940
Maximum System
Operating Pressure
Bar
10
10
10
(1)
Based on units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% Ethylene Glycol.
All performance data supplied in accordance with BBS EN14511-1:2013
(2)
EER = DX Cooling Output / (Compressor input power + Fan Input Power),
(3)
Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options fitted please refer to Airedale.
(4)
For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations
(5)
Ambient temperature that full Freecool capacity can be achieved
DCF Mechanical Data Extra Quiet