Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
115
Chiller Technical Manual 7267818 V1.13.0_01_2018
Fre
eC
oo
l
ELECTRICAL DATA
28
29
30
Unit Data
DCF073TR-13GPPY
DCF078TR-14GPYY
DCF082TR-13HYYV
Nominal Run Amps
(1)
A
451.7
481.7
528.1
Maximum Start Amps
A
715.1
745.1
795.5
Recommended Mains Fuse Size
A
500
500
560
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (EC)
Quantity
13
14
13
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 59.2 / 47.9
59.2 / 47.9 / 47.9
47.9 / 47.9 / 55.2
Quantity
2 + 2 + 3
2 + 3 + 3
3 + 3 + 3
Motor Rating
kW
36.2 / 36.2 / 29.8
36.2 / 29.8 / 29.8
29.8 / 29.8 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 298 / 326
298 / 326 / 326
326 / 326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
426.9
458.0
498.6
Reactive power reduction/saving
(4) kVAr
45.5
44.1
53.9
Maximum Start Amps
A
690.3
721.4
766.0
Recommended Mains Fuse Size
A
500
500
560
Electronic Soft-start
Nominal Run Amps
A
451.7
481.7
528.1
Maximum Start Amps
A
584.7
614.7
665.1
Recommended Mains Fuse
A
500
500
560
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
426.9
458.0
498.6
Maximum Start Amps
A
559.9
591.0
635.6
Recommended Mains Fuse Size
A
500.0
500.0
560.0
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
28.5
28.5
Unit Nominal Run Amps
A
472.7
509.9
556.4
Recommended Mains Fuse Size
A
500
560
630
Motor Rating
kW
12.1
16.4
16.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
28.5
35.0
35.0
Unit Nominal Run Amps
A
480.0
516.4
562.9
Recommended Mains Fuse Size
A
500
560
630
Motor Rating
kW
16.4
20.3
20.3
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
26.9
26.9
Unit Nominal Run Amps
A
467.8
503.7
550.0
Recommended Mains Fuse Size
A
500
560
630
Motor Rating
kW
12.4
16.8
16.8
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
33.2
33.2
Unit Nominal Run Amps
A
473.6
508.8
555.1
Recommended Mains Fuse Size
A
500
560
630
Motor Rating
kW
16.8
20.7
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet
Содержание DeltaChill
Страница 1: ...Technical Manual DeltaChill Air Cooled DeltaChill Free Cooling Chiller 500kW 1000kW ...
Страница 300: ...Chillers Introduction DeltaChill Air Cooled and FreeCool 300 Chiller Technical Manual 7267818 V1 13 0_01_2018 Technical ...
Страница 301: ...Chillers DeltaChill Air Cooled and FreeCool Introduction 301 Chiller Technical Manual 7267818 V1 13 0_01_2018 Technical ...