Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
211
Chiller Technical Manual 7267818 V1.13.0_01_2018
A
ir C
oo
led
ELECTRICAL DATA
173
174
175
Unit Data
DCC070TX-19GPPY
DCC074TX-20GPYY
DCC080TX-19GYYV
Nominal Run Amps
(1)
A
474.9
504.9
535.0
Maximum Start Amps
A
738.3
768.3
810.6
Recommended Mains Fuse Size
A
500
560
560
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (EC)
Quantity
19
20
21
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 59.2 / 47.9
59.2 / 47.9 / 47.9
47.9 / 47.9 / 47.9
Quantity
2 + 2 + 3
2 + 3 + 3
3 + 3 + 3
Motor Rating
kW
36.2 / 36.2 / 29.8
36.2 / 29.8 / 29.8
29.8 / 29.8 / 29.8
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 298 / 326
298 / 326 / 326
326 / 326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
450.2
481.3
512.4
Reactive power reduction/saving
(4)
kVAr
45.6
44.3
42.9
Maximum Start Amps
A
713.6
744.7
788.0
Recommended Mains Fuse Size
A
500
560
560
Electronic Soft-start
Nominal Run Amps
A
474.9
504.9
535.0
Maximum Start Amps
A
607.9
637.9
680.2
Recommended Mains Fuse
A
500
560
560
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
450.2
481.3
512.4
Maximum Start Amps
A
583.2
614.3
657.6
Recommended Mains Fuse Size
A
500
560
560
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
485.9
515.9
545.9
Recommended Mains Fuse Size
A
560
560
560
Motor Rating
kW
6.2
6.2
6.2
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
21.2
Unit Nominal Run Amps
A
495.9
525.9
555.9
Recommended Mains Fuse Size
A
560
560
630
Motor Rating
kW
12.1
12.1
12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
10.2
10.2
10.2
Unit Nominal Run Amps
A
483.2
513.3
543.4
Recommended Mains Fuse Size
A
560
560
560
Motor Rating
kW
6.4
6.4
6.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
19.8
Unit Nominal Run Amps
A
491.1
521.2
551.3
Recommended Mains Fuse Size
A
560
560
630
Motor Rating
kW
12.4
12.4
12.4
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Extra Quiet