Notes: Units DCF055DX-14DPV0 DCF057DX-14DYY0 DCF059DX-15DYV0
SEPR
1,3,5
6.76
6.63
6.68
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
548876
581165
598626
Rated Refrigerant Capacity
P
A
1,3,5 kW
500.6
519.7
540.1
Rated Power Input D
A
kW
161.0
172.7
177.1
Rated EER
DC,A
3.11
3.01
3.05
Declared Refrigerant Capacity P
B
1,3,5 kW
563.9 / 461.3
491.2 / 397.9
505.4 / 412.1
Declared Power Input D
B
kW
133.3 / 106.7
117.6 / 92.1
119.9 / 94.4
Declared EER
DC,B
4.23 / 4.32
4.18 / 4.32
4.22 / 4.37
Declared Refrigerant Capacity P
C
1,3,5 kW
501.8 / 387.3
533.8 / 431.5
549.1 / 446.8
Declared Power Input D
C
kW
89.4 / 68.8
98.4 / 76.7
100.2 / 78.5
Declared EER
DC,C
5.61 / 5.63
5.42 / 5.62
5.48 / 5.69
Declared Refrigerant Capacity P
D
1,3,5 kW
396.9 / 260.7
413.2 / 334.9
429.4 / 342.0
Declared Power Input D
D
kW
39.3 / 40.1
42.1 / 50.9
43.4 / 52.1
Declared EER
DC,D
10.10 / 6.49
9.83 / 6.58
9.90 / 6.57
SSCEE
2,3,5
%
167.1
171.6
172.1
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
504.2
522.2
542.7
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
500.6
519.7
540.1
Declared EER
d
35°C
3.11
3.01
3.05
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
563.9 / 461.3
491.2 / 397.9
505.4 / 412.1
Declared EER
d
30°C
4.23 / 4.32
4.18 / 4.32
4.22 / 4.37
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
501.8 / 387.3
533.8 / 431.5
549.1 / 446.8
Declared EER
d
25°C
5.61 / 5.63
5.42 / 5.62
5.48 / 5.69
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
396.9 / 260.7
413.2 / 334.9
429.4 / 342.0
Declared EER
d
20°C
10.10 / 6.49
9.83 / 6.58
9.90 / 6.57
Sound Power Level LWA
dB(A)
Air flow rate
m³/h
201476
201476
215867
Off mode P
OFF
kW
0.157
0.157
0.157
Thermostat-off mode P
TO
kW
4.049
2.940
3.161
Standby Mode P
SB
kW
0.289
0.301
0.306
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
Technical Data
Ecodesign
DCF055DX-14DPV0, DCF057DX-14DYY0, DCF059DX-15DYV0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
Introduction
DeltaChill™ Air Cooled and FreeCool
296
Chiller Technical Manual 7267818 V1.13.0_01_2018
Te
ch
ni
ca
l
Содержание DeltaChill
Страница 1: ...Technical Manual DeltaChill Air Cooled DeltaChill Free Cooling Chiller 500kW 1000kW ...
Страница 300: ...Chillers Introduction DeltaChill Air Cooled and FreeCool 300 Chiller Technical Manual 7267818 V1 13 0_01_2018 Technical ...
Страница 301: ...Chillers DeltaChill Air Cooled and FreeCool Introduction 301 Chiller Technical Manual 7267818 V1 13 0_01_2018 Technical ...