ELECTRICAL DATA
73
74
75
Unit Data
DCF075TX-14GPYY
DCF059DX-15DYV0
DCF061DX-16DVV0
Nominal Run Amps
(1)
A
481.7
384.7
413.0
Maximum Start Amps
A
745.1
652.1
680.4
Recommended Mains Fuse Size
A
500
450
450
Evaporator
Immersion Heater Rating
W
250
170
170
Condenser Fan - Per Fan (EC)
Quantity
14
15
16
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 47.9 / 47.9
47.9 / 55.2
55.2 / 55.2
Quantity
2 + 3 + 3
3 + 3
3 + 3
Motor Rating
kW
36.2 / 29.8 / 29.8
29.8 / 33.1
33.1 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 326 / 326
326 / 326
326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
458.0
362.8
384.0
Reactive power reduction/saving
(4) kVAr
44.1
39.8
51.1
Maximum Start Amps
A
721.4
630.2
651.4
Recommended Mains Fuse Size
A
500
450
450
Electronic Soft-start
Nominal Run Amps
A
481.7
384.7
413.0
Maximum Start Amps
A
614.7
521.7
550.0
Recommended Mains Fuse
A
500
450
450
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
458.0
362.8
384.0
Maximum Start Amps
A
591.0
499.8
521.0
Recommended Mains Fuse Size
A
500
450
450
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
21.2
Unit Nominal Run Amps
A
502.6
405.7
434.1
Recommended Mains Fuse Size
A
560
450
450
Motor Rating
kW
12.1
12.1
12.1
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
509.9
413.0
441.4
Recommended Mains Fuse Size
A
560
450
500
Motor Rating
kW
16.4
16.4
16.4
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
19.8
19.8
Unit Nominal Run Amps
A
497.9
400.8
428.9
Recommended Mains Fuse Size
A
560
450
450
Motor Rating
kW
12.4
12.4
12.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
503.7
406.5
434.6
Recommended Mains Fuse Size
A
560
450
500
Motor Rating
kW
16.8
16.8
16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.