5.6.3
IEC 61850 - Interface
The ICD-File contains the data model, resp. describes the functionality of the according
SYNCHROTACT 5 – device. An IEC 61850 System Engineering Tool configures the
ICD-Files of all participants in a specific application and their connections among each
other and deposits them in a SCD-File.
The SYN61850Config-Tool can finally download the SCD-File to the SYNCHROTACT 5
– device.
SYN61850Config-Tool
IED
y
IED
x
Communication and Application System
Engineering Tool
S10003
IED
SYNCHROTACT
Application z
ICD-File
SYNCHROTACT 5
SCD-File
Application z
The data sets are fix and must not be changed at any time, neither during configuration
time nor during operation (see also tables with logical nodes in chapter 4.3.8).