![ABB SYN 5201 Скачать руководство пользователя страница 57](http://html.mh-extra.com/html/abb/syn-5201/syn-5201_operating-instructions-manual_4831057.webp)
Operating Instructions
SYN 5201/SYN 5202
Document No Art Part
Language Revision
page
abb
ABB Switzerland Ltd
3BHS109762 E01
en D 57
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
Resolution of the bit-coded words into individual binary signals:
Address 1 (Index 0):
Bit Binary
signal
0 Start
1 Stop
2 Release
DB
3
Reset (cancel fault and set to "READY")
4
Blocking input BLK REM (read only!)
5 --
6 --
7 --
8
Configurable digital input 1 (only with SYN 5014)
9
Configurable digital input 2 (only with SYN 5014)
10
Configurable digital input 3 (only with SYN 5014)
11
Configurable digital input 4 (only with SYN 5014)
12
Configurable digital input 5 (only with SYN 5014)
13
Configurable digital input 6 (only with SYN 5014)
14
Configurable digital input 7 (only with SYN 5014)
15 --
Address 2 (Index 1):
Bit Binary
signal
0
LED ‘
U<
Umax‘
1 LED
‘s<smax‘
2
LED ‘
<
max‘
3 LED
‘U1/U2=0‘
4 --
5 --
6 --
7 --
8
Relay for configurable digital output 1
9
Relay for configurable digital output 2
10
Relay for configurable digital output 3
11
Relay for configurable digital output 4
12
Relay for configurable digital output 5
13
Relay for configurable digital output 6
14
Relay for configurable digital output 7
15 --
Address 3 (Index 2):
Bit Binary
signal
0 LED
‘ERROR‘
1 LED
‘BLOCKED‘
2 LED
‘READY‘
3 LED
‘OPERATING‘
4 LED
‘U+‘
5 LED
‘U-‘
6 LED
‘f+‘
7 LED
‘f-‘
8 LED
‘COMMAND‘
9
LED ‘CHK RELEASE‘
10 ‘COMMAND‘
relay
11 --
12 --
13 --
14 --
15 --