10.4 Transmission
values
10.4.1 Measuring
ranges
Channel 1
Voltage
U1, U2
0 to 1.30*Un
Phase-angle difference
-179 to +180 DEG
Frequency
f1, f2
10 to 100Hz
Slip
s
0 to 50 %
Acceleration
ds/dt
0 to 10 %/s
Paralleling time
t on
0 to 1 s
Channel 2 (synchrocheck)
Voltage
U1, U2
0 to 1.30*Un
Phase-angle difference
-179 to +180 DEG
Frequency
f1, f2
10 to 100Hz
Slip
s
0 to 50 %
10.4.2 Accuracy
Measuring accuracy channel 1
Voltage U1,
U2
0.1 V
Voltage difference
U
0.15 V
Phase-angle difference
1 DEG at s
0.5 %
Frequency f1,
f2
50 mHz
Slip s
0.02 %
Operating accuracy channel 1
Maximum and minimum voltage
Umax, Umin
0.3 V
Maximum voltage difference
Umax
0.35 V
Phase coincidence
2 DEG bei s
0.5 %
Slip limit
smax
0.03 %
Paralleling time
t on
10 ms
Paralleling command duration
tp on
10 ms
Monitoring time
t supervis
1 s
Blocking time after selection
t block
100 ms
Channel 2 (synchrocheck)
Voltage U1,
U2
5 %
Voltage difference
U
1 %
Phase-angle difference
2 DEG
Slip s
0.1 %