4.2.8
Configuration parameters (Option)
Digital inputs I1 to I7 and digital outputs O1 to O7
Normally, the configuration is fixed prior to commissioning. The settings are therefore
based on the project planning data.
The following table shows all possible functions for the
inputs
:
Setting
value
Function
Remarks
±1 ***
Paralleling point 1 and Parameter set 1
±2
Paralleling point 2 and Parameter set 2
±3
Paralleling point 3 and Parameter set 3
The parameter set is only selected if no other
±4
Paralleling point 4 and Parameter set 4
input programmed with values from 8 to 14 is
±5
Paralleling point 5 and Parameter set 5
active.
±6
Paralleling point 6 and Parameter set 6
±7
Paralleling point 7 and Parameter set 7
±8
Parameter
set
1
±9
Parameter set 2
These programming settings are only required if
±10
Parameter set 3
the number of parameter sets and the number of
±11
Parameter set 4
paralleling points differ.
±12
Parameter set 5
(see examples in section 5.4)
±13
Parameter set 6
±14
Parameter set 7
±15
Selection of TEST mode
Normal synchronizing, but the paralleling relay is
not operated. A configurable output relay with the
value 16 can be used in its place (see below).
±16
Blocking of synchronizing process
A running synchronizing process is stopped and
is continued when the signal is dropped.
±17
Blocking of synchronizing process delayed by
t block
A running synchronizing process is stopped. After
the signal is dropped, the time t block elapses,
then the synchronizing process is automatically
continued.
±18
Stop synchronization
Second Stop command
±19
Start synchronization
Second Start command
±20
Cancel fault and set device to “Ready”
If an error is detected, the device automatically
changes to the status ‘Blocked with error‘. This
function can be used to cancel the error and
return the device to readiness for operation.
±21
No function
±22
No function
±23
No function
±24
No function
±25
No function
±26
No function
±27
No function
±28
No function
±29
No function
±30
No function
±31
No function
±32
No function
*** The "+" in front of the setting value indicates that the related function via operating
control interface will be blocked as long as the blocking input "BLK REM" is active. A "-"
in front of the setting value indicates that blocking of the function is disabled not (see
section 5.6.2).
Note