Operating Instructions
SYN 5201/SYN 5202
Document No Art Part
Language Revision
page
abb
ABB Switzerland Ltd
3BHS109762 E01
en D 56
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
4.3.5 Addressing
Lon-Bus
29 words, each with 16 bits, are transmitted. The addressing is as follows:
Add-
ress
Content Word
type Direction
of trans-
mission
Format
Scaling
Signal name
1
Digital inputs
Bit-coded
read*
--
--
NV_Syn5_inputs_out
2 Digital
outputs
Bit-coded
read
--
--
NV_Syn5_output1
3 Digital
outputs
Bit-coded
read
--
--
NV_Syn5_output2
4
Actual value
U
Analog val. read
signed integer**
0.1 % of Un
NV_Syn5_delta_U
5
Actual value
Analog val. read
signed integer
0.1 DEG
NV_Syn5_alpha
6
Actual value s
Analog val. read
signed integer
0.01 %
NV_Syn5_slip
7
Actual value U1
Analog val. read
signed integer
0.1 % of Un
NV_Syn5_U1
8
Actual value U2
Analog val. read
signed integer
0.1 % of Un
NV_Syn5_U2
9
Actual value f1
Analog val. read
signed integer
0.01 Hz
NV_Syn5_f1
10
Actual value f2
Analog val. read
signed integer
0.01 Hz
NV_Syn5_f2
11
Actual value ds/dt
Analog val. read
signed integer
0.01 %/s
NV_Syn5_ds_dt
12 Back-indication of selected
parameter set
Analog val. read
unsigned integer *** Number of the
selected parameter set
NV_Syn5_Parameterset
13 Software
version
Analog val. read
unsigned integer
One digit of the version
number per nibble (half
byte)
(e.g.: 5137d = 1411h =
V1.4.1.1)
NV_Syn5_SW_version
14
Command counter reading par-set 1 Analog val. read
unsigned integer
none (0 to 65535)
NV_Syn5_close1
15
Command counter reading par-set 2 Analog val. read
unsigned integer
none (0 to 65535)
NV_Syn5_close2
16
Command counter reading par-set 3 Analog val. read
unsigned integer
none (0 to 65535)
NV_Syn5_close3
17
Command counter reading par-set 4 Analog val. read
unsigned integer
none (0 to 65535)
NV_Syn5_close4
18
Command counter reading par-set 5 Analog val. read
unsigned integer
none (0 to 65535)
NV_Syn5_close5
19
Command counter reading par-set 6 Analog val. read
unsigned integer
none (0 to 65535)
NV_Syn5_close6
20
Command counter reading par-set 7 Analog val. read
unsigned integer
none (0 to 65535)
NV_Syn5_close7
21
Current event (event code)
Analog val. read
unsigned integer
none
NV_Syn5_event_code
22
Year of the current event
Analog val. read
unsigned integer
none
NV_Syn5_event_year
23
Month of the current event
Analog val. read
unsigned integer
none
NV_Syn5_event_month
24
Day of the current event
Analog val. read
unsigned integer
none
NV_Syn5_event_day
25
Hour of the current event
Analog val. read
unsigned integer
none
NV_Syn5_event_hour
26
Minute of the current event
Analog val. read
unsigned integer
none
NV_Syn5_event_minute
27
Second of the current event
Analog val. read
unsigned integer
none
NV_Syn5_event_second
28
Hundredth of a second of the current
event
Analog val. read
unsigned integer
none
NV_Syn5_one_hundredth
29
Digital inputs
Bit-coded
write
--
--
NV_Syn5_inputs
*
read = read data from SYNCHROTACT 5
**
signed integer = whole numbers
***
unsigned integer = positive whole numbers