Operating Instructions
SYN 5201/SYN 5202
Document No Art Part
Language Revision
page
abb
ABB Switzerland Ltd
3BHS109762 E01
en D 53
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
4.3.3
Addressing Profibus DP
28 words, each with 16 bits, are transmitted. The addressing is as follows:
Add-
ress
Content Word
type
Direction
of trans-
mission
Format
Scaling
1
Digital inputs
Bit-coded
read and
write*
-- --
2 Digital
outputs
Bit-coded
read --
--
3 Digital
outputs
Bit-coded
read --
--
4
Actual value
U
Analog value
read
signed integer**
0.1 % of Un
5
Actual value
Analog value
read
signed integer
0.1 DEG
6
Actual value s
Analog value
read
signed integer
0.01 %
7
Actual value U1
Analog value
read
signed integer
0.1 % of Un
8
Actual value U2
Analog value
read
signed integer
0.1 % of Un
9
Actual value f1
Analog value
read
signed integer
0.01 Hz
10
Actual value f2
Analog value
read
signed integer
0.01 Hz
11
Actual value ds/dt
Analog value
read
signed integer
0.01 %/s
12 Back-indication of selected
parameter set
Analog value
read unsigned
integer
***
Number of the selected
parameter set
13 Software
version
Analog value
read
unsigned integer One digit of the version
number per nibble (half
byte)
(e.g.: 5137d = 1411h =
V1.4.1.1)
14
Command counter reading parameter set 1
Analog value
read
unsigned integer none (0 to 65535)
15
Command counter reading parameter set 2
Analog value
read
unsigned integer none (0 to 65535)
16
Command counter reading parameter set 3
Analog value
read
unsigned integer none (0 to 65535)
17
Command counter reading parameter set 4
Analog value
read
unsigned integer none (0 to 65535)
18
Command counter reading parameter set 5
Analog value
read
unsigned integer none (0 to 65535)
19
Command counter reading parameter set 6
Analog value
read
unsigned integer none (0 to 65535)
20
Command counter reading parameter set 7
Analog value
read
unsigned integer none (0 to 65535)
21
Current event (event code)
Analog value
read unsigned
integer
none
22
Year of the current event
Analog value
read unsigned
integer
none
23
Month of the current event
Analog value
read unsigned
integer
none
24
Day of the current event
Analog value
read unsigned
integer
none
25
Hour of the current event
Analog value
read unsigned
integer
none
26
Minute of the current event
Analog value
read unsigned
integer
none
27
Second of the current event
Analog value
read unsigned
integer
none
28
Hundredth of a second of the current
event
Analog value
read unsigned
integer
none
*
read = read data from SYNCHROTACT 5
**
signed integer = whole numbers
***
unsigned integer = positive whole numbers