![ABB SYN 5201 Скачать руководство пользователя страница 34](http://html.mh-extra.com/html/abb/syn-5201/syn-5201_operating-instructions-manual_4831034.webp)
Operating Instructions
SYN 5201/SYN 5202
Document No Art Part
Language Revision
page
abb
ABB Switzerland Ltd
3BHS109762 E01
en D 34
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
4.1.5 Configuration
parameters
“Config parameters“ (option)
These allow different functions to be assigned to the inputs and outputs (see also
section 4.2.8 and 5.4).
“Digital inputs “
No. Parameter
name
Symbol
Range/resolution Unit
Default
setting
1.
Digital input 1
I 1
0 to 32
- 1
2.
Digital input 2
I 2
0 to 32
- 2
3.
Digital input 3
I 3
0 to 32
- 3
4.
Digital input 4
I 4
0 to 32
- 4
5.
Digital input 5
I 5
0 to 32
- 5
6.
Digital input 6
I 6
0 to 32
- 6
7.
Digital input 7
I 7
0 to 32
- 14
“Digital outputs “
No. Parameter
name
Symbol
Range/resolution Unit
Default
setting
1.
Digital output 1
O 1
0 to 32
- 1
2.
Digital output 2
O 2
0 to 32
- 2
3.
Digital output 3
O 3
0 to 32
- 3
4.
Digital output 4
O 4
0 to 32
- 4
5.
Digital output 5
O 5
0 to 32
- 5
6.
Digital output 6
O 6
0 to 32
- 6
7.
Digital output 7
O 7
0 to 32
- 15
4.1.6
Synchrocheck parameters (SYN 5202 only)
These are the parameters for the second channel.
Synchrocheck parameters “synchrocheck param “
No.
Parameter name
Symbol
Range/resolution
Unit
Default setting
1.
Slip limit
smax
0.1 to 2.0
%
0.5
2. Angle
limit
max
5 to 40/5
DEG
15
3. Maximum
voltage difference
Umax
5 to 40/5
%
5
4.
Maximum zero voltage
U0max
0 to 50/5
%
50
5.
Nominal voltage
Un
50 to 130/5
VAC
110
4.1.7
Linking of the parameter sets in dual channel systems
The parameter set of the second channel is linked with the active parameter set of the
first channel.
S01002
SYN 5202/ SYN 5302
Synchrocheck
Channel 1
Parameter set 1
Parameter set 2
Parameter set 3
Parameter set 4
Parameter set 5
Parameter set 6
Parameter set 7
Channel 2