9.3.9 Status
display IEC 61850
LED 1: Error
Color Description
Remarks
Red
Indicates that an internal error
occurred on the IEC 61850,
communication module
No application present or
processor error
1. Turn off and back on
auxiliary voltage
2. Check if the
communication module
has the right software
Otherwise communication
module is defective
LED 2: Supply
Color Description
Remarks
Green
Supply OK
Normal state
LED 3: Transmission indication
Color State
Description
Remarks
Yellow flashing
Indicates data traffic to the
IEC 61850
communication
module
SYNCHROTACT 5 –
communication is functioning
Yellow off
No data traffic to the
IEC 61850
communication
module
SYNCHROTACT 5 –
communication does not
function
1. Turn off and back on
auxiliary voltage
2. Check if the
communication module
has the right software
3. Check the plug
connection between
communication module
and busprint SYN 5010
Otherwise communication
module is defective
LED 1
LED 2
LED 4
LED 3
LED 5
LED 6