![ABB SYN 5201 Скачать руководство пользователя страница 105](http://html.mh-extra.com/html/abb/syn-5201/syn-5201_operating-instructions-manual_4831105.webp)
Operating Instructions
SYN 5201/SYN 5202
Document No Art Part
Language Revision
page
abb
ABB Switzerland Ltd
3BHS109762 E01
en D 105
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
Error
Code
Description
Remarks
Remedy
080 Contact
monitoring
triggered
The paralleling
command contacts have
not opened again
following the last
command!
Caution
: Ensure that the circuit
breaker does not close
accidentally! Check paralleling
command circuits
081
Active Start signal blocks
switchover to “Ready”
SYNCHROTACT 5 can
only be brought into
Ready status if no Start
signal is active.
Cancel Start signal
082
Active blocking signal
prevents Start
Blocking signal must
have dropped on rising
edge of the Start signal
Cancel blocking signal
Parameter set selection
Code
Description
Remarks
101
Select parameter set 1
The display appears immediately after the Start command
(<1 s) or if the corresponding signal is active in “Blocked“
status
102
Select parameter set 2
The display appears immediately after the Start command
(<1 s) or if the corresponding signal is active in “Blocked“
status
103
Select parameter set 3
The display appears immediately after the Start command
(<1 s) or if the corresponding signal is active in “Blocked“
status
104
Select parameter set 4
The display appears immediately after the Start command
(<1 s) or if the corresponding signal is active in “Blocked“
status
105
Select parameter set 5
The display appears immediately after the Start command
(<1 s) or if the corresponding signal is active in “Blocked“
status
106
Select parameter set 6
The display appears immediately after the Start command
(<1 s) or if the corresponding signal is active in “Blocked“
status
107
Select parameter set 7
The display appears immediately after the Start command
(<1 s) or if the corresponding signal is active in “Blocked“
status