4.1.2 Event
logger
The events are displayed in the following format (for meaning, see also section 9):
Line number
Timestamp
Event code
000
001
.
.
.
255
hh:mm:ss
. . .
. . .
. . .
. . .
. . .
Cyyy
.
.
.
.
.
4.1.3 Actual
values
The following table shows the actual values and their position in the menu:
Actual values
No. Actual
value
name
Symbol
Range/resolution
Unit
1. Voltage difference
U
0.0 to 99.9
%
2. Phase-angle difference
-179 to +180
DEG
3.
Slip
s
0.00 to 50.00
%
4.
Voltage U1
U1
0 to 130*Un
%
5.
Voltage U2
U2
0 to 130*Un
%
6.
Frequency f1
f1
10.0 to 100.0
Hz
7.
Frequency f2
f2
10.0 to 100.0
Hz
8.
Acceleration
ds/dt
0.00 to 9.99
%/s
9.
Selected parameter set
Pset selected
1 to 7
-
10.
Software version
xxxx
-
-
11.
Command counter parameter set 1
CLOSE 1
0 to 65535
1
12.
Command counter parameter set 2
CLOSE 2
0 to 65535
1
13.
Command counter parameter set 3
CLOSE 3
0 to 65535
1
14.
Command counter parameter set 4
CLOSE 4
0 to 65535
1
15.
Command counter parameter set 5
CLOSE 5
0 to 65535
1
16.
Command counter parameter set 6
CLOSE 6
0 to 65535
1
17.
Command counter parameter set 7
CLOSE 7
0 to 65535
1
4.1.4
Parameter sets 1 to 7
1 parameter set is provided in the basic version, with 7 parameter sets available as an
option. The structure is the same in all parameter sets. The 7th parameter set only
differs from the others in the setting values, in that the default settings are pre-set for
synchrocheck operation.
In addition, each parameter is divided into seven functional parameter groups:
1. Actual value calibration
2. Command generation
3. Paralleling conditions
4. Dead bus conditions
5. Voltage matcher
6. Frequency matcher
7. General parameters
Each group contains the parameters associated with this function.