While the synchronizing process is running, changes in the parameter set selection
are ignored.
Stopping the synchronizing process:
Normally, the synchronizing process is terminated by means of an auxiliary contact
of the circuit breaker (normally open). The signal is passed to the Stop input of the
SYNCHROTACT 5.
In exceptional cases, a synchronizing process needs to be terminated without
closing the circuit breaker. In this case, a parallel Stop command is sent to the
SYNCHROTACT 5 (triggered manually or automatically).
The Stop signal should be at least 0.5 seconds long (recommended length: 1 to 2 s),
can, however, also be active up until the start of a new synchronizing process.
Locking:
Start and Stop are locked. Stop has priority.
5.4 Configurable
I/Os
In the version with 7 parameter sets, the SYN 5014 board with seven digital inputs and
outputs is fitted. Normally, each of the seven inputs and outputs is assigned a parameter
set and a paralleling point (default setting), i.e., the inputs and outputs should not be
configured. The following examples show special cases where a configuration is
required. If no configuration is required (normal case!), it can be continued in section
5.5.
S00016
1
2
3
4
5
6
7
1
2
3
4
5
6
7
2
4
3
5
7
6
Parameter
set
selec
tion
Paralleling
point s
e
lect
ion
Parameter set 1
Note