Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
10.5 Environmental
values
10.5.1 Isolation
Dielectric test
IEC 60255-5
2 kV
Impulse voltage withstand test
IEC 60255-5
5 kV
10.5.2 Climatic
stability
Temperature ranges for devices without communication:
Transport/storage
-40 to +85 °C
Functionable
-25 to +70 °C
Operation (compliance with technical data)
-10 to +55 °C
Temperature ranges for devices with communication:
Transport/storage
-10 to +85 °C
Functionable
+5 to +70 °C
Operation (compliance with technical data)
+5 to +55 °C
Tests:
Cold
IEC 60068-2-1
-25 °C
Dry heat
IEC 60068-2-2
+70 °C; 16 h
Damp heat, steady state
IEC 60068-2-3
Ca 4 days
Damp heat, cyclic
IEC 60068-2-30
55 °C/2 cycles
Change of temperature
IEC 60068-2-14
Nb; 1°C/min.
10.5.3 Mechanical
stability
Vibration
Vibration response
Endurance
IEC 60255-21-1
10 to 150 Hz; Cl. 2
1 g
2 g
Shocks and bumps
Shock response
Withstand
Bump
IEC 60255-21-2
class 2
10 g
30 g
20 g
Earthquake
Single-axis sine sweep seismic test
IEC 60255-21-3
IEEE STD 344-1987
Method A
5g in each axis
10.5.4
Interference immunity/transmission (EMC)
Emission AC mains
(conducted disturbance)
CISPR 22
Class B
0
.
15..0,5 MHz: 66..56 dB/56..46 dB
0.5..5 MHz: 56 dB / 46 dB
5..30 MHz: 60 dB / 50 dB
Emission enclosure
(radiation disturbance)
CISPR 11
Class A
30..230 MHz: 30 dB
230..1000MHz: 37 dB
Electrostatic discharges
IEC 60255-22-2
IEC 61000-4-2
IEEE C37.90.3-2001
Class IV
Contact: 8 kV
Air: 15 kV