LED 4: Ready Indication
Color Description
Remarks
Green
Indicates that the IEC 61850
communication module is
ready for operation
ca. 90 s after Power up
LED 5: Ethernet-Connection Indication (Link)
Color Description
Remarks
Dark No
connection
Yellow
10 Mbps Connection
Transmission speed is defined by
Green
100 Mbps Connection
outstation
LED 6: Ethernet-Transmission Indication (Activity)
Color Description
Remarks
Dark
No transmission
No transmission is taking place
Yellow
Half-duplex transmission
Data packets are sent or
received successively
Green
Full-duplex transmission
Data packets can be sent or
received simultaneously
9.4 Disturbances
related
to time synchronizing
Devices with the optional IEC 61850-interface (see type code chapter 3.1) contain a
clock. If the time synchronizing is configured to „enabled“ by means of the
SYN61850Config-Tool, this clock overwrites the time and date of the SYNCHROTACT 5
- clock, even when no SNTP-Server is connected. (see chapter 2.7).
Note