-X12:8
-X12:9
-X12:7
OUT 7
CB 1
Manual paralleling
switch
IN 1
IN 2
IN 7
COMMAND
-X6:1
-X6:2
OUT 2
-X11:3
-X11:4
OUT 1
-X11:1
-X11:2
-X10:2
-X10:1
-X10:4
-X10:3
-X10:14
-X10:13
-
+
-
+
+
-
-
Manual paralleling
switch
CB 2
CB 1
CB 2
MAN
SYN 520X
See section 5.5 "Use of the automatic synchronizing device as synchrocheck" for
parameter settings for operation as synchrocheck.
5.4.2
Assigning one parameter set to several paralleling points
This case applies if, for example, several identical circuit breakers/generators are
paralleled under the same conditions.
Example:
One parameter set
is assigned to
two paralleling points
:
A signal which activates parameter set 1 is permanently present at input IN1. If a signal
is applied to input IN2 before Start, paralleling point 1 is activated, a signal at IN3 selects
paralleling point 2.
Programming:
Parameter I1 = I8
Parameter I2 = 1
Parameter I3 = 2
Parameter O2 = 1
Parameter O3 = 2
Operating behaviour:
Signal to:
Outputs:
Selected:
Inputs IN1 and IN2
OUT2 closes
Parameter set 1 and paralleling point 1
Inputs IN1 and IN3
OUT3 closes
Parameter set 1 and paralleling point 2
5.4.3
Further configuration options
When the inputs and outputs are not used for selecting parameter sets and paralleling
points, they can be used for other functions e.g. for signaling or additional control
commands (see tables in section 4.2.8 from value 15 on).
Note