![ABB SYN 5201 Скачать руководство пользователя страница 115](http://html.mh-extra.com/html/abb/syn-5201/syn-5201_operating-instructions-manual_4831115.webp)
Operating Instructions
SYN 5201/SYN 5202
Document No Art Part
Language Revision
page
abb
ABB Switzerland Ltd
3BHS109762 E01
en D 115
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
9.3.8
Status display Lon-Bus
LED 1
Color Description
Remarks
-- --
Not
used
LED 2, Service LED
Color Status
Description
Remarks
Green flashing
Application installed, but not
(yet) configured for the
network.
SYNCHROTACT 5
communications board is
runnable, but still needs to be
configured (Service key)
Green on
No application installed, and
not configured for the network.
Indicates errors which were
detected by the Neuron Self-
Test Routine.
SYNCHROTACT 5
communications board is not
runnable (internal problem in
device). Try to cancel the error
as follows:
1. Switch auxiliary voltage off
and on again
2. Check whether the right
software is loaded into the
communications module
3. Check plug connection
between the
communications module
and the SYN 5010 base
board.
Otherwise the communications
module is defective.
Green off
Configured and installed in a
network.
No fault!
LED 3, Error
Color Description
Remarks
--
Indicates that an internal error
has occurred in the
communications module.
Try to cancel the error by
switching the auxiliary voltage
off and on.
LED 4, Wink
Color Description
Remarks
--
Indicates that the node has
received a LonWorks Wink
command.
i.e. an internal diagnostic
check is currently taking place.
LED 1
LED 2
LED 3
LED 4