Frequency matcher with variable pulse durations
The frequency matcher issues a command the length of which is proportional to the
current slip. The proportionality factor df/dt can be adapted to the governor. The
frequency matcher aims at a value midway between the nearer slip limit and zero. The
adjusting command length tpf is:
dt
df
s
s
tpf
/
2
max
Between 1/3 and 2/3 of smax there is a range where no adjustment takes place. The
adjusting pulse is discontinued as soon as the slip passes through zero. The command
length does not fall below a settable minimum value. After an adjusting command, the
system waits for the set pulse interval ts f so that the actual values can stabilise to the
new setpoint.
S00005
df
dt
tp f
ts f
-smax
s = 0
1/2*(+smax)
+smax
s
t
Time
Adjusting pulse
Pulse interval time
Speed (Slip)
Slip
Set point governor
Range w/o adjusting pulses over-synchronous
a
dmi
ss
ib
le
paral
le
ling
range
Range w/o adjusting pulses sub-
synchronous
Range for lower commands
Range for higher commands
Range for lower commands
sub-
sy
nc
hro
nous
ra
nge
ov
er-s
yn
ch
rono
us
ran
ge
Slip
S00004
-smax
2/3*(-smax)
1/3*(-smax)
1/3*(+smax)
2/3*(+smax)
+smax
s = 0
s
Range for raise pulses
Range for lower pulses
Range for raise pulses
Range for lower pulses