Operation, configuration and communication
22
Sensyflow iG, Version 1.00
42/14-39 EN
7.1.2
Module configuration for cyclic data communication (DP)
Sensyflow iG provides cyclic data communication for the following modules, which are described in the
vendor-specific GSD file.
Four modules must be selected for cyclic data communication. Observe the following slot assignment for
configuring the modules.
• Slot 1: Empty_Module, Mass flow
• Slot 2: Empty_Module, Gas temp.
• Slot 3: Empty_Module, Total, SET_Total, SET/MODE_Total, Characteristics Input
• Slot 4: Empty_Module, Characteristics Input
Module
No.
Module
Byte
Input
Data type
Input
Byte
Output
Data type
Output
1
Empty_Module
-
0
-
0
2
Mass flow
5 Byte
(Float +
Status]
Byte 0..3 Float
Byte 4 Status
-
0
3
Gas temp.
5 Byte
(Float +
Status]
Byte 0..3 Float
Byte 4 Status
-
0
4
Total
5 Byte
(Float +
Status]
Byte 0..3 Float
Byte 4 Status
-
0
5
SET_Total
5 Byte
(Float +
Status]
Byte 0..3 Float
Byte 4 Status
1 Byte
Byte 0
0=Totalize
1=Reset 2=PRESET
6
SET/MODE_Total
5 Byte
(Float +
Status]
Byte 0..3 Float
Byte 4 Status
2 Byte
Byte 0
0=Totalize
1=Reset 2=PRESET
Byte 1
0-2=Totalize
3= HOLD
7
Characteristics Input -
0
7 Byte,
(2 Byte,
Float +
Status)
Byte 0
Bit 0..3
0x0 = characteristic 1
0x1 = characteristic 2
0x2 = characteristic 3
0x3 = characteristic 4
Bit 4..6 reserved
Bit 7
0x0 = change characteristic
0x1 = characteristic active
Byte 1
Bit 0..3
0x0 = Start
0x1 = Halt
0x3 = Preset
0x4 = Reset
Byte 2 (reserved)
Byte 3..6
Float Integrator value