Operation, configuration and communication
48
Sensyflow iG, Version 1.00
42/14-39 EN
Submenu level 2
→
AI GAS TEMP MENU
Display indication
Designation according to PA profile
3.0
Explanation
AI TEMP STATE
AI TEMP STATE
D
Display of status message for gas temperature in hexadecimal notation (status to AI
GAS TEMP Block)
Display 0x80 … 0x83
→
OK; (see also section 7.1.2.2 and 7.1.2.3 )
TEMP PV_SCALE HIGH
PV_SCALE_HIGH
SE
internal 100 % value, normally upper range value
TEMP PV_SCALE LOW
PV_SCALE_LOW
SE
internal 0 % value, normally lower range value
OUT_SCALE AT 100%
OUT_SCALE_AT 100%
SE
external 100 % value
OUT_SCALE AT 0%
OUT_SCALE_AT 0%
SE
external 0 % value
TEMP FAILSAFE TYPE
FSAFE_TYPE
SP
If the device detects an error by means of the status signal, one of the following two
options can be selected for the output TEMP signal:
LAST VALID VALUE the last valid measuring value
ERROR VALUE the current measuring value
ERROR SUBSTITUTION VALUE a selectable substitution value
TEMP FAIL VALUE
FSAFE_VALUE
SP
Arbitrary numeric value as substitution for an incorrect measuring value. This is only
sent to the output if option ERROR SUBSTITUTION VALUE has been selected in
TEMP ERROR SIGNAL.
TEMP FILTER FACTOR
PV_FTIME
SP
Filter factor for signal attenuation, adjustable between 0.2 s and 100 s
TEMP HYSTERESIS
ALARM_HYS
SP
Hysteresis for limit value monitoring, input in the selected temperature unit
(e. g. 5 °C)
TEMP ALARM HIGH
HI_HI_LIM
SP
Upper alarm limit; alarm is triggered if limit is exceeded by measuring value
TEMP WARNING HIGH
HI_LIM
SP
Upper warning limit (pre-alarm); warning is issued if measuring value exceeds limit
TEMP WARNING LOW
LO_LIM
SP
Lower warning limit (pre-alarm); warning is issued if measuring value falls below
limit
TEMP ALARM LOW
LO_LO_LIM
SP
Lower alarm limit; alarm is triggered if measuring value falls below limit
TEMP SIMULATION
SIMULATE
SP
Outputting TEMP simulation values ON or OFF
(incl. STATUS QUALITY and STATUS LIMIT)
(
Note: ON produces the symbol "S" in the display)
TEMP SIMUL. VALUE
SP
Input of the TEMP simulation value
STATUS QUALITY
SP
Simulation of the STATUS signal, selection from the signals described in section
7.1.2.2 and 7.1.2.3
GOOD OK,
GOOD UPDATE EVENT…
STATUS LIMIT
SP
Simulation of the limit value STATUS, selection between
OK
LOW_LIMIT
HIGH_LIMIT
CONSTANT
END AI GAS TEMP