Appendix: Manufacturer-specific GSD file (Device data file)
58
Sensyflow iG, Version 1.00
42/14-39 EN
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
Redundancy = 0
; no redundancy transmission
Repeater_Ctrl_Sig = 0
24V_Pins = 0
;===================================================================
; Slave specific Data
;===================================================================
Freeze_Mode_supp
= 1
; no Freeze_Mode_supp, support in later version
Sync_Mode_supp
= 1
; no Sync_Mode_supp, support in later version
Auto_Baud_supp =
1
Set_Slave_Add_supp =
1
Min_Slave_Intervall
= 50
; Slave Intervall-Time 5 ms
;===================================================================
; Bitmap, Order No, ASIC
;===================================================================
Implementation_Type = "SPC3"
Bitmap_Device = "ABB05CAn"
; symbolic representation in standard cases
Bitmap_Diag = "ABB05CAd"
;symbolic representation for diagnostic cases
Bitmap_SF = "ABB05CAs"
; symbolic representation in spec. oper. modes
OrderNumber = "Automation Products" ; user defined keyword, known in COM Profibus
;===================================================================
; Ext_User_Prm_Data_Ref
;===================================================================
Max_User_Prm_Data_Len
= 3
Ext_User_Prm_Data_Const(0)
= 0x84,0x00,0x00; DPV1 parameters
;DPV1 status1
= 0x84 =>
; Bit2
= 0 WD_Base=10ms (1ms=1)
; Bit7
= 1 DPV1 Enable (Disable = 0)
;DPV1 status2
= 0x00 =>
; Bit0
= 0 ChkCfg nach EN50170(User specific = 1)
;DPV1 tatus3
= 0x00 =>
; alarm not implemented
;===========================================================================
; Module Definition
;===========================================================================
Modular_Station =
1
Max_Module
= 4
Max_Input_Len
= 15
; 4 x ( 4 Byte real Status Byte)
Max_Output_Len
= 9
; 1 Byte Gas Character 1 Byte Total. no Profile 3.0
+ 4 Byte real 1 Byte Status
; + 2 Byte Total
Max_Data_Len
= 24
; Max_Outp Max_Input_Len
Max_Diag_Data_Len
= 14
Slave_Family
= 3
; no specification
;Gerätespezifische Diagnose Byte 1
Unit_Diag_Bit(24) = "Hardware failure"
Unit_Diag_Bit(25) = "Reserved"
Unit_Diag_Bit(26) = "Reserved"
Unit_Diag_Bit(27) = "Electromic Temp. to high"
Unit_Diag_Bit(28) = "Memory error"
Unit_Diag_Bit(29) = "Sensor failure"
Unit_Diag_Bit(30) = "Device not initialized"
Unit_Diag_Bit(31) = "Selfcalibration failed "