Operation, configuration and communication
42/14-39 EN
Sensyflow iG, Version 1.00
49
Submenu level 2
→
TOTAL MENU
In case of power failure the integrator value is retained. After switching the device on again, adding continuous automatically.
Display indication
Designation according to PA profile
3.0
Explanation
TOTAL STATE
TOTAL_STATUS
D
Display of status message for the integrator in hexadecimal notation (sta-
tus to TOTAL Block)
Display 0x80 … 0x83
→
OK
(see also section
7.1.2.2
and
7.1.2.3
)
TOTAL UNIT
UNIT_TOT
SP
Unit of integrator value, select from
kg, g, lb, Nm
3
, Nl, SCF
TOTAL SET
SET_TOT
SP
Select from
TOTAL normal integrator function
RESET TOTAL Reset integrator value to 0
PRESET TOTAL Preset an integrator value
TOTAL RUN/STOP
MODE_TOT
SP
Select from
HOLD stop
TOTAL Normal function
TOTAL FAILSAFE TYPE
FAIL_TOT
SP
Select from
RUN continue with faulty measuring value
HOLD integrator stops
MEMORY continue with last valid mass flow value
TOTAL PRESET VALUE
PRESET_TOT
SP
Manually entered starting value of integrator
Default = 0
TOTALO ALARM HIGH
HI_HI_LIM
SP
Upper alarm limit; alarm is triggered if limit is exceeded by measuring va-
lue
TOTAL WARNING HIGH
HI_LIM
SP
Upper warning limit (pre-alarm); warning is issued if measuring value ex-
ceeds limit
END OF TOTAL MENU