Electrical installation
18
Sensyflow iG, Version 1.00
42/14-39 EN
5.4
Connecting PROFIBUS DP via PROFIBUS M12 bus connector
Fig. 5-3 PROFIBUS DP M12 bus connector
For this device version a PROFIBUS DP M12 bus connector with complete internal wiring is supplied in-
stead of the central screw terminals (
see Fig. 5-2
). The bus connection is made via a T-plug that connects
the incoming and outgoing PROFIBUS cable. This version allows pulling the T-plug and disconnecting
the device from PROFIBUS DP without interfering with the bus operation.
Note
Suitable T-plugs and cable sockets/plugs are available as accessories.
(see Sensyflow iG data sheets and PROFIBUS accessories)
DP M12 connecting socket
DP M12
1
2
3
4
5
Plug
T-piece
Socket
Pin
Signal
Description
1
VP
Supply voltage, positive (P 5 V)
2
RxD/TxD-N
Receive/transmit data, –N, line A (green wire)
3
DGND
Data transmission potential (reference potential for VP)
4
RxD/TxD-P
Receive/transmit data, positive, line B (red wire)
5
Shield
Shield/protective earth
Thread
Shield
Shield/protective earth