83
High speed and instantaneous phase
overcurrent protection (HSOC, IOC)
&KDSWHU
&XUUHQW
Only detailed network studies can determine the operating conditions under which the
highest possible fault current is expected on the line.
Also study transients that could cause a high increase of the line current for short times.
A typical example is a transmission line with a power transformer at the remote end,
which can cause high inrush current when connected to the network and can thus also
cause the operation of the instantaneous, overcurrent protection.
Calculate the maximum current I
fB
at the relay site for faults at the end of the protected
line, see figure 42. The calculation should be done using the minimum source imped-
ance values for Z
A
and in the case of meshed systems, the maximum source impedance
values for Z
B
in order to get the maximum through fault current from A to B.
)LJXUH 7KURXJKIDXOWFXUUHQWIURP$WR%,
I%
For meshed systems with strong infeed from station B, also calculate the maximum
through fault current I
fA
for faults at station A. In order to get the maximum through
fault current, the minimum value for Z
B
and the maximum value for Z
A
have to be con-
sidered.
The relay must not trip for any of the two through fault currents. Hence the minimum
theoretical current setting (Imin) will be:
(Equation 28)
A safety margin of 30% is recommended. Hence the minimum primary setting (Is) for
the instantaneous phase overcurrent IOC is:
99000474.vsd
~
~
Z
A
Z
B
Z
L
A
B
Relay
I
fB
Fault
Imin
MAX I
fA
I
fB
,
(
)
≥
Содержание REO 517
Страница 10: ... RQWHQWV ...
Страница 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Страница 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Страница 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Страница 100: ...90 Time delayed phase and residual overcurrent protection TOC1 KDSWHU XUUHQW Equation 36 Iset IsSEC I1b 100 ...
Страница 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Страница 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Страница 171: ...161 About this chapter KDSWHU RQWURO KDSWHU RQWURO ERXW WKLV FKDSWHU This chapter describes the control functions ...
Страница 293: ...283 About this chapter KDSWHU RJLF KDSWHU RJLF ERXW WKLV FKDSWHU This chapter describes the logic functions ...
Страница 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Страница 379: ...369 About this chapter KDSWHU 0HWHULQJ KDSWHU 0HWHULQJ ERXW WKLV FKDSWHU This chapter describes the metering functions ...
Страница 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Страница 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Страница 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...