68
3 zone impedance protection (Z(n)RW)
&KDSWHU
/LQHLPSHGDQFH
•
The effect of a load transfer between the terminals of the protected line. When the
fault resistance is considerable, the effect must be recognized.
•
Zero-sequence mutual coupling from parallel lines.
Usually, these errors require a limitation of the underreaching zone (normally zone 1)
to 85-90% of the protected line. For the same reason, it is necessary to increase the reach
of the overreaching zone (normally zone 2) to at least 120% of the protected line - to
ensure that the overreaching zone always covers a complete line. The zone 2 reach can
be even higher, but in general it should never exceed 80% of the following impedances:
•
The impedance corresponding to the protected line, plus the first zone reach of the
shortest adjacent line.
•
The impedance corresponding to the protected line, plus the impedance of the max-
imum number of transformers operating in parallel on the bus at the remote end of
the protected line.
The back-up overreaching zone (normally zone 3) must never exceed 90% of the short-
est zone 2 reach of any of the lines connected to the remote end bus. It must be at least
2 times the zone 1 reach.
The reverse zone is applicable for purposes of scheme communication logic. The same
applies to the back-up protection of the busbar or power transformers. It is necessary to
secure, that it always covers the overreaching zone, used at the remote line terminal for
the telecommunication purposes.
In the case of a long line followed by a short line, or by a large bank of low impedance
transformers, the mandatory 120% setting might overreach zone 1 of the adjacent line,
or reach through the transformer bank at the other line end. In such cases, one must in-
crease the zone 2 time delay and thus secure the selectivity. The zone 2 reach must not
be reduced below 120% of the protected line section. It must be covered under all con-
ditions.
(DUWKUHWXUQFRPSHQVDWLRQLQWZRSKDVHV\VWHPV
A measurement loop with single-phase to earth fault consists of three impedances,
which are shown in figure 35, where:
Z
1
:
impedance in phase conductor
R
F
:
fault resistance
Z
N
:
earth return impedance
Содержание REO 517
Страница 10: ... RQWHQWV ...
Страница 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Страница 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Страница 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Страница 100: ...90 Time delayed phase and residual overcurrent protection TOC1 KDSWHU XUUHQW Equation 36 Iset IsSEC I1b 100 ...
Страница 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Страница 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Страница 171: ...161 About this chapter KDSWHU RQWURO KDSWHU RQWURO ERXW WKLV FKDSWHU This chapter describes the control functions ...
Страница 293: ...283 About this chapter KDSWHU RJLF KDSWHU RJLF ERXW WKLV FKDSWHU This chapter describes the logic functions ...
Страница 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Страница 379: ...369 About this chapter KDSWHU 0HWHULQJ KDSWHU 0HWHULQJ ERXW WKLV FKDSWHU This chapter describes the metering functions ...
Страница 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Страница 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Страница 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...