66
3 zone impedance protection (Z(n)RW)
&KDSWHU
/LQHLPSHGDQFH
The input signal Z1RW-VTSZ, which is normally connected from the fuse failure su-
pervision function, is activated when ac voltage failure has been discovered in the sec-
ondary circuits between the voltage instrument transformers and the terminal. The
signal is deactivated when the fuse failure supervision function is disabled.
The binary signal Z1RW-BLKTR prevents the impedance function in zone 1 from
sending a tripping signal. Different external signals can be connected to the input for
this purpose.
The three logical output signals from the impedance function for zone 1 are:
•
Z1RW-START, which shows that underimpedance (Forward, Reverse or Non-di-
rectional) has been registered by zone 1.
•
Z1RW-NDST, which shows that underimpedance (non-directional) has been regis-
tered by zone 1.
•
Z1RW-TRIP, which gives the tripping order from the measuring element for zone
1.
The corresponding signals are also available in zone 3. Zone 2 (two phase version) has
three additional non-directional output start signals:
•
Phase-to-earth-fault phase L1 or L2.
•
Phase-to-phase fault
These signals may be used as phase selector information in the fault locator.
The output signals can be connected to the binary outputs and other functions in
REO 517.
&DOFXODWLRQV
The parameters for the impedance function are set via the local HMI or PST (Parameter
Setting Tool). Refer to the Technical reference manual for setting parameters and path
in local HMI.
The settings for the distance protection function must correspond to the parameters for
the protected line and also correspond with the selective plan for the network.
All settings are of the secondary value, which is why it is necessary to recalculate the
primary line impedance to the secondary side of the current and voltage transformers.
Содержание REO 517
Страница 10: ... RQWHQWV ...
Страница 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Страница 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Страница 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Страница 100: ...90 Time delayed phase and residual overcurrent protection TOC1 KDSWHU XUUHQW Equation 36 Iset IsSEC I1b 100 ...
Страница 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Страница 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Страница 171: ...161 About this chapter KDSWHU RQWURO KDSWHU RQWURO ERXW WKLV FKDSWHU This chapter describes the control functions ...
Страница 293: ...283 About this chapter KDSWHU RJLF KDSWHU RJLF ERXW WKLV FKDSWHU This chapter describes the logic functions ...
Страница 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Страница 379: ...369 About this chapter KDSWHU 0HWHULQJ KDSWHU 0HWHULQJ ERXW WKLV FKDSWHU This chapter describes the metering functions ...
Страница 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Страница 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Страница 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...