72
Automatic switch onto fault logic (SOTF)
&KDSWHU
/LQHLPSHGDQFH
$XWRPDWLFVZLWFKRQWRIDXOWORJLF627)
$SSOLFDWLRQ
The switch-onto-fault function is a complementary function to impedance measuring
functions.
With the switch-onto-fault (SOTF-) function, a fast trip is achieved for a fault on the
whole line, when the line is being energized. The SOTF tripping is generally non-direc-
tional in order to secure a trip at fault situations where directional information can not
be established, for example, due to lack of polarizing voltage when a line potential
transformer is used.
Automatic activation can be used only when the potential transformer is situated on the
line side of a circuit breaker.
)XQFWLRQDOLW\
The switch-onto-fault function can be activated either externally or automatically, in-
ternally, by using the information from a dead-line-detection (DLD) function (see fig-
ure 37).
)LJXUH 627)IXQFWLRQVLPSOLILHGORJLFGLDJUDP
After activation, a distance protection zone (usually its non-directional starting signal)
is allowed to give an instantaneous trip. The functional output signal from the distance
protection zone to be used should be connected to the SOTF-NDACC functional input
of the SOTF function, see figure 37. The distance protection zone used together with
the switch-onto-fault function shall be set to cover the entire protected line. The non-
directional instantaneous condition is maintained for 1 s after closing the line circuit
breaker.
S O T F -B C
S O T F -D L C N D
&
S O T F -N D A C C
t
2 0 0 m s
> 1
&
S O T F -B L O C K
t
1 0 0 0 m s
&
t
1 5 m s
S O T F -T R IP
e n 0 0 0 0 0 4 9 2 .vs d
Содержание REO 517
Страница 10: ... RQWHQWV ...
Страница 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Страница 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Страница 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Страница 100: ...90 Time delayed phase and residual overcurrent protection TOC1 KDSWHU XUUHQW Equation 36 Iset IsSEC I1b 100 ...
Страница 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Страница 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Страница 171: ...161 About this chapter KDSWHU RQWURO KDSWHU RQWURO ERXW WKLV FKDSWHU This chapter describes the control functions ...
Страница 293: ...283 About this chapter KDSWHU RJLF KDSWHU RJLF ERXW WKLV FKDSWHU This chapter describes the logic functions ...
Страница 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Страница 379: ...369 About this chapter KDSWHU 0HWHULQJ KDSWHU 0HWHULQJ ERXW WKLV FKDSWHU This chapter describes the metering functions ...
Страница 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Страница 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Страница 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...